Differential
Control
Differential control is a special case of ratio control. With
differential control, as with ratio, the set point of one channel
is determined by the process variable value of another channel.
The set point of the differential channel is calculated by adding
an offset (
Set Point Offset
) to the process variable value of the
master channel. The
Set Point Ratio
parameter is set to 1.
Remote Set Point
Remote set point is implemented in the PPC as a special case
of ratio control. As with ratio control, the set point of a channel
is set by multiplying an analog input value by a ratio (
Set Point
Ratio
) and adding an offset (
Set Point Offset
). Typically, however,
the analog input is not used as feedback for closed-loop control,
so there is no master channel. The
Max Set Point
and
Min Set Point
parameters may be used to limit the set point value. Setup
remote set point according to the instructions for ratio control.
Logic
Programs
The PPC-2000 is able to run not only the closed-loop control
program but also a user-written logic program.
LogicPro
is a
software program that runs under Windows95/98/NT. This
logic programming tool can be used to customize the function of
the PPC-2000 controller. Any of the digital and analog I/O as
well as all of the controller parameters can be accessed and
changed by user written logic programs. Logic programs are
stored along with the controller firmware in nonvolatile
memory. Consult the
LogicPro User’s Guide
for specific
instructions on how to write, compile and download logic
programs to the PPC-2000.
NOTE!
If an output variable in a logic program sets a value
using an IO Driver and IO Physical Address, the
associated register in the PPC-2000 cannot be written
to by the closed-loop control program, an HMI or any
other device.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...