LD Offset
Designate an offset value that determines the low deviation
alarm limit relative to the current set point. The low deviation
alarm occurs when the process variable is lower than the
channel set point less this value. The alarm limit changes when
the set point changes. The default low deviation alarm offset is
0
.
Range: same as the range of the input type selected. See
LD Type
Set the function of the low deviation alarm. See
for a description of the settings.
Range:
Alarm
or
Control
LD Enable
Set this field to enable or disable the low deviation alarm.
When it is Enabled, the low deviation alarm activates if the
process variable (PV) dips below set point by more than the
LD
Offset
. The PV must rise above the low deviation limit plus the
alarm deadband to be reset (cleared). When this parameter is
set to
Disabled
, the low deviation alarm does not occur.
Range:
Enable
or
Disable
LD Output Dest
Choose a digital output to toggle when the low deviation alarm
occurs. This may be any available hardware output or Soft
Boolean register accessible by the logic program. The default
for this parameter is
Not Assigned
. Outputs that are already
assigned to control output destinations will be rejected. The
same output may not be used for multiple alarm output
destinations.
Range:
Not Assigned,
or any of the digital outputs on the
DigI/O
spreadsheet, or any of the
Soft Bool
registers.
LP Limit
Set the low process alarm limit. An alarm occurs when the
process variable is less than this value. This value does not
change when the set point changes. The default low process
alarm set point is
0
.
Range: same as the range of the input type selected. See
LP Type
Select the function of the low process alarm. See
for a description of the settings.
Range:
Alarm
or
Control
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...