Heat/Cool Scale Lo
Set this parameter in conjunction with
Heat/Cool Scale Hi
to scale the output or to change the control
action. (See table 3.x.) Enter the value, as a percent of range, that the output should approach as the
process variable approaches the set point from below for a heat output or from above for a cool output.
See Figure 3.x.
The default and typical value is 0%. For example, as a heater raises the temperature of a load towards
set point, the output decreases toward 0%. In some cases it is desirable that the output never reach 0%,
in that case enter a minimum value greater than 0%.
Range:
0.0
to
100.0%
Heat/Cool Scale Hi
Set this parameter in conjunction with
Heat/Cool Scale Lo
to scale the output or to change the control
action. (See table 3.x.) Enter the value, as a percent of range, that the output should approach as the
process variable moves away from the set point either upward for a heat output or downward for a cool
output. See Figure 3.x.
The default and typical value is 100%. For example, as the temperature of a heated system drops the
controller increases its output toward 100%. In some cases it is desirable that the output never reach
100%, in that case enter a maximum value less than 100%. See also
Auto Heat/Cool Limit
.
Range:
0.0
to
100.0%
Note
Sometimes it is necessary for a heat output to
increase
as the process variable approaches the set point
from below. In such cases the
Heat/Cool Scale Lo
value is set above the
Heat/Cool Scale Hi
parameter.
(See Direct Heat in Table 3.x.) For example, in some systems heat is added outside the control loop and
the heat output controls a cooling water flow. In such a system as the temperature rises to set point, the
output increases to flow more water and slow the heating process.
Table 3.x Output Scaling Parameters Settings and Control Action
Output
Control Action
Scale Lo
Scale Hi
Note
Heat
Reverse (Default)
0%
100%
Cool
Reverse
100%
0%
As the process variable increases,
the output decreases.
Heat
Direct
100%
0%
Cool
Direct (Default)
0%
100%
As the process variable increases,
the output increases.
CAUTION
When a
Heat/Cool Scale Lo
parameter is set to a value
greater
than the corresponding
Heat/Cool Scale
Hi
, the
Heat Output %
or
Cool Output %
values are inversely related to the actual output signal. In this
case when the
Heat/Cool Output %
indicates 0% the output is
fully on
regardless of whether the
Control
Mode
is set to Auto, Manual or Tune. Always remove power from the controller before servicing any
components.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...