Signal Common
Each controller and the converter should be connected to the
signal common to insure they can properly interpret the signals
on the network. Pin #1 in the RJ12 connectors connects the
signal commons of all the PPCs to each other. At the converter
connect the signal common to the common of the converter’s DC
power supply.
The communications ports are optically isolated from the
sensors and the rest of the PPC circuitry, so connecting the
communications commons together will not create a ground
loop.
Termination
In some installations, particularly when transmission lines are
long, the transmission lines must be terminated. The receive
lines at the converter or host device should be terminated in the
converter, the connector to the host device, or the device itself.
Typically the converter documentation provides instructions
for termination.
The PPC receive lines can be terminated by setting a jumper on
the last PPC-2010 module. To terminate the lines for port 1, set
jumper JU1 on the last PPC-2010 module on the network to the
A position. This places a 120 ohm resistor across the receive
lines. To terminate the line for port 2, set jumper JU2 on the
last PPC-2010 module on the network to the A position. This
places a 120 ohm resistor across the receive lines. See
2010 Jumper Settings on page 18
Alternately, the line may be terminated externally on the 485
terminal block by placing a termination resistor across the
receive line screw terminals near the last PPC. See
. The value of the termination resistor should be
equal to the impedance of the communications cable used.
Values are typically 120 to 200 ohm.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...