Chapter 5: LogicPro and Modbus Reference
PPC-2000 User’s Guide
162
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
Accessing the Database with Modbus
Each register can be individually accessed using software and
the Modbus communications protocol via a serial port on the
processor module because each register has a unique Modbus
address. The Modbus address for each parameter is given in
sections
Analog and Counter Input Parameters in the Database
Global Parameters in the Database on
Because the database is quite large, it is impractical and
undesirable to list each Modbus address. Instead, the first and
last addresses for each parameter are listed. Individual
registers are addressed by determining the offset from the first
address corresponding to the particular input, output, or
channel.
For example, in a PPC-2000 system with 32 analog inputs on
one module, the register addresses for inputs 1-32 are 30601 to
30632. The measured value corresponding to the first analog
input is stored at address 33601. The value of the second input
is stored at address 33602. The value of input 26 is stored at
address 30626, and so on. The
Database Offset
for the first
analog input is said to be 1, for the second input is 2, and for the
26th input is 26. In each section describing a database table,
the
Database Offset
scheme is explained.
How LogicPro Accesses the Database
Logic programs can be written and downloaded using
LogicPro
.
Typically, such programs access digital and/or analog
I/O and may also access other values stored in the database.
Because the user-written logic program resides in the processor
module, it does not use the serial port or Modbus to access the
database. Instead, each register can be accessed by logic
program variables using one of the I/O drivers supplied with
LogicPro
.
Some drivers correspond to modules. These drivers are used to
access the digital and analog I/O values corresponding to the
field devices connected to each module. The
LogicPro
IO Physical Address is used in conjunction with these
module-specific drivers to use a digital or analog I/O value in a
logic program.
For example, the value measured by a thermocouple attached
to the first input on an Analog In module with address 2 is
accessed with the Analog_In_202x driver and the Logic Pro IO
Physical Address 2.1.
The
LogicPro
Database driver facilitates access to all database
parameters. Because the database is large, it impractical and
undesirable to list each
LogicPro
address. Instead, the
parameter number and database offset range for each
parameter are supplied. Individual registers are addressed by
coupling the parameter number and the database offset
corresponding to the particular input, output, or channel.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...