WARNING

Lubricants

Do NOT use Vaseline, oils, hydrocarbon lubricants or spray silicone anywhere! Petroleum base lubricants 

will cause swelling of o-rings and seals. The use of other lubricants may attack plastic Noryl®. It is recom

-

mended that Dow Corning® silicone grease be used as a lubricant for all control valves. Dow Corning® 7 

Release Compound is used in the manufacture of Chandler Systems control valves. (Part # LT-150)

Sealants

Pipe dope and liquid thread sealers may contain a carrier that attacks some plastic materials. It is recom

-

mended that Teflon® tape be used to seal plastic Noryl® threaded fittings.

Provectr Plus Specifications

-How the Provectr Plus Works-

The Provectr Plus requires no chemicals for its operation. It consists of two components: (1) AP tank with 

air compressor and (2) filter tank. The first item serves to oxidize and precipitate iron and sulfur so that the 

filter can later remove them. The water flows down through the mineral bed of the filter and out the service 

lines. The collected precipitates must be regularly removed from the filter by reversing the flow of water 

through the filter running to drain. Called “backwashing” and lasting 10 minutes, the process expands the 

mineral freeing the iron, sulfur, manganese and turbidity, which are washed out of the filter to the drain. It 

is important that the correct amount of water is available for the Backwash Cycle. Check pumping capacity 

to be certain water is available in sufficient volume to adequately backwash the equipment at the specified 

rate.  

General Specifications

AF10AC-3

AF12AC-3

AF13AC-3

AF14AC-3

Filter Media Type

SmartBlend ™

Filter Media Capacity (cu ft)

1.5

2.0

2.5

3.0

Provectr

®

 Tank Size 

10 x 54

10 x 54

10 x 54

16 x 40

Mineral Tank Size

10 x 54

12 x 52

13 x 54

13 x 65

Service Flow Rate - Continuous (gpm)

5

6

8

9

Service Flow Rate - Intermittent (gpm)

7

8

10

11

Backwash Flow Rate (gpm)

5.0

6.0

7.0

7.0

Gallons Used / Backwash

100

120

140

140

Space Required (D x W x H) per tank

10 x 10 x 62

10 x 10 x 62

10 x 10 x 62

16 x 16 x 73

Approximate Shipping Weight (lbs)

175

246

280

321

Summary of Contents for Provectr Plus AF10AC-3

Page 1: ...Provectr Plus Installation Operation Manual...

Page 2: ...Assembly Page 17 Service Instructions Page 18 Troubleshooting Page 19 Error Codes Page 20 Warranty Information Page 21 FCC Compliance Statement http www chandlersystemsinc com files FCC_Compliance_St...

Page 3: ...wn through the mineral bed of the filter and out the service lines The collected precipitates must be regularly removed from the filter by reversing the flow of water through the filter running to dra...

Page 4: ...will notice an 8 foot meter cord and plug attached Note If household plumbing is galvanized and you intend to make an installation with copper or vice ver sa obtain dielectric unions to prevent dissi...

Page 5: ...ypass valve indicate proper direc tion of water flow Install inlet and outlet piping in direction of arrows It is recommended that a vacuum breaker be installed on the inlet plumbing 1 Position AP tan...

Page 6: ...soaked while preparing the installation and will pre vent the control valve from being plugged with floating material on initial backwash H Remove funnel and clean filter material from tank threads I...

Page 7: ...ou hear and feel the O Ring pop into place before inserting the clip 2 Install 1 2 I D drain line tubing not included from hose barb to an open drain A 4 gap between end of the drain line and the open...

Page 8: ...cal supply to be certain the cord is connected to an uninterrupted 115 volt outlet 3 REGISTER YOUR PRODUCT at www watersoftinc com 4 Leave this manual with the homeowner Important Notice The plumbing...

Page 9: ...eft off prior to the power interruption When used without battery back up during a power failure the unit stops at its current point in the regeneration position and then restarts at that point when t...

Page 10: ...th the Menu Enter button After the entire display flashes press the Menu Enter button to move to the next menu item 2 Regeneration Cycle Step Times Steps 1 2 3 4 Example 3 10 The next 4 displays set t...

Page 11: ...the default password the first time you connect to it the app will ask you to enter the password After entering it the first time you should not need to enter it again unless it changes 3 BTLE Valve d...

Page 12: ...ms in ORANGE with a set button can be changed For Filters Set Backwash Frequency This sets the amount of day between backwash cycles Change Time of Day Press SET to set time automatically based on dev...

Page 13: ...p Option 2 Touch any graph to enlarge and see details Enlarged graphs are able to be zoomed in by pinching with two fingers Enlarged graph shown below Regenerate Unit at Next Regen Time button This wi...

Page 14: ...Encoder 20001X124 1 3 Front Plate 20001X004 1 4 Encoder Wheel 20001X007 1 5 Main Gear 21001X120 1 6 Power Supply 20001X125 1 7 Back Plate 20001X005 1 8 Lower Front Base For Cover 20111X002 1 9 Motor 2...

Page 15: ...15 Valve Body Drive Assy 2 1 3 18 19 28 12 17 16 4 8 9 10 11 14 15 13 24 20A 20B 26 27 21 25 22 16 23 5 7 6 6 6 6A...

Page 16: ...5 1 12 10 24 X 1 Screw SST 20001X226 2 13 3 8 Push Lock Plug 20009X010 1 14 Injector Cap 20009X001 1 15 Injector Seal 20001X224 1 16 Injector Plug O Ring Assy 20001X217 1 17 Injector Screen 20001X222...

Page 17: ...its 20017X284 3 1 Female Straight Slip Set optional 20017X288 4 1 NPT Straight Set optional 20017X289 5 3 4 NPT Straight Set optional 20017X307 6 1 X 3 4 Brass Sweat Connector Set optional 20017X304 7...

Page 18: ...cover C To Replace Piston Assembly 1 Follow steps A1 A3 2 Disconnect the meter signal wire from the circuit board 3 Remove lower back base screws and detach lower back base 4 Remove screw and washer...

Page 19: ...als Replace motor if motor is unresponsive F To Replace Meter 1 Follow steps A1 A3 2 Unplug meter cable from front of circuit board 3 Unscrew meter assembly nut from valve body 4 Remove meter from val...

Page 20: ...wheel for debris 2 Cycle power Valve should either find home or go to a different error code If error 4 returns replace powerhead assembly Error 5 Motor overload This occurs when the motor current is...