![WaterLogic WL400 Series Manual Download Page 67](http://html2.mh-extra.com/html/waterlogic/wl400-series/wl400-series_manual_3662927067.webp)
WL400
Manual Page 67
–
Revision: 10-23-2019
4.
Compressor is Not Running
Possible Reason
Solution
Green Heater and Compressor
Switch button on unit is in the
off position
Turn Green Heater and Compressor Switch on.
I = ON
Compressor Starting Circuit
Turn Green Heater and Compressor Switch off.
O =
OFF.
Remove the compressor cap on side of the
compressor;
Disconnect the black and red terminal connectors;
Inspect the starter and overload relay for any
defects.
Replace components(s) as needed.
Turn Green Heater and Compressor Switch on.
I = ON and
retest compressor operation.
Summary of Contents for WL400 Series
Page 34: ...WL400 Manual Page 34 Revision 10 23 2019 WL400 BASE MAIN PARTS DRAWING AND PARTS LIST...
Page 42: ...WL400 Manual Page 42 Revision 10 23 2019 BASE CABINET SIDE REMOVAL...
Page 43: ...WL400 Manual Page 43 Revision 10 23 2019 BASE CABINET CONFIGURATION...
Page 45: ...WL400 Manual Page 45 Revision 10 23 2019 INSIDE LEFT SIDE CABINET CONFIGURATION...
Page 46: ...WL400 Manual Page 46 Revision 10 23 2019 INSIDE RIGHT SIDE CABINET CONFIGURATION...