5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Operating Parameters cont.
Cooling Mode
Entering
Load Temp (
o
F)
Entering
Source Temp (
o
F)
Suction
Pressure (psig)
Discharge
Pressure (psig)
Superheat
(
o
F)
Subcooling
(
o
F)
50
30
86-99
135-160
12-22
2-15
50
92-107
191-214
10-19
4-15
70
98-115
248-268
5-15
6-16
90
101-119
335-367
6-15
8-16
110
105-122
425-465
8-16
10-19
70
30
89-106
131-163
15-20
3-6
50
103-125
194-223
11-15
6-9
70
118-143
257-273
11-15
9-12
90
125-151
344-381
8-12
12-14
110
135-155
280-315
8-16
10-19
90
30
92-113
128-166
15-20
3-6
50
115-143
197-233
11-15
6-9
70
129-158
266-294
11-15
9-12
90
145-165
350-390
20-30
8-19
110
160-180
360-400
25-35
7-16
110
30
96-121
125-170
55-65
2-20
50
127-161
200-243
41-52
4-18
70
158-200
275-315
21-38
8-19
90
155-175
360-400
30-40
5-15
110
170-195
460-500
25-35
5-15
Notes: Operating parameters at 3 gpm/ton source and load flow. 7/8/2014
Consult the Capacity Tables for each 504W11 OptiHeat model for normal allowable operating conditions.
Some of the conditions shown above are outside of the compressor operational limits for specific models.