33
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Operating Limits
Operating Limits
Cooling
Heating
°F
°C
°F
°C
Source Side Water Limits
Minimum Entering Water
30
-1.1
20
-6.7
Normal Entering Water
85
29.4
60
15.6
Maximum Entering Water
110
43.3
90
32.2
Load Side Water Limits
Minimum Entering Water
50
10.0
60
15.6
Normal Entering Water
60
15.6
100
37.8
Maximum Entering Water
90
32.2
140
60
NOTES:
Minimum/maximum limits are only for start-up
conditions, and are meant for bringing the space up to
occupancy temperature. Units are not designed to operate
at the minimum/maximum conditions on a regular basis. The
operating limits are dependant upon three primary factors: 1)
entering source temperature, 2) entering load temperature,
and 3) flow rate (gpm). When any of the factors are at the
minimum or maximum levels, the other two factors must be at
the normal level for proper and reliable unit operation. Consult
the Capacity Tables for each model to determine allowable
normal operating conditions. Units are not designed for
outdoor installation.
Flow Rates
Model
040
050
066
Compressor (1 each)
Scroll
Factory Charge R410A, oz [kg]
94 [2.66]
108 [3.06]
142 [4.02]
Coax & Piping Water Volume - gal [l]
1.0 [3.94]
1.4 [5.25]
1.6 [6.13]
Weight - Operating, lb [kg]
305 [138.3]
340 [154.2]
360 [163.3]
Weight - Packaged, lb [kg]
320 [145.1]
355 [161.0]
375 [170.0]
7/8/14
Physical Data
Source/Load Flow Rates
MODEL
MINIMUM OPEN LOOP
FLOW RATE
MINIMUM CLOSED
LOOP FLOW RATE
NORMAL SOURCE
FLOW RATE
MAXIMUM
FLOW RATE
040
5.0
8.0
10.0
12.0
050
8.0
12.0
15.0
17.0
066
10.0
14.0
19.0
21.0
7/8/14