24
5 SERIES OPTIHEAT 504W11 INSTALLATION MANUAL
Aurora ‘Base’ Control
NOTE:
Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora
Interface and Diagnostics (AID) Tool for additional information.
Control Features
• Random start at power up
• Anti-short cycle protection
• High and low pressure cutouts
• Loss of charge
• Water coil freeze detection
• Over/under voltage protection
• Load shed
• Emergency shutdown
• Diagnostic LED
• Test mode push button switch
• Alarm output
• Accessory output with N.O. and N.C.
• Two Modbus communication ports
Field Selectable Options via Hardware
DIP Switch (SW1)
– Test/Configuration Button (See SW1
Operation Table)
Test Mode
The control is placed in the test mode by holding the push
button switch SW1 for 2 - 5 seconds. In test mode most of
the control timings will be shortened by a factor of sixteen
(16). LED3 (green) will flash at 1 second on and 1 second
off. Additionally, when entering test mode LED1 (red) will
flash the last lockout one time. Test mode will automatically
time out after 30 minutes. Test mode can be exited by
pressing and holding the SW1 button for 2 to 5 seconds or
by cycling the power.
NOTE:
Test mode will automatically
be exited after 30 minutes.
Reset Configuration Mode
The control is placed in reset configuration mode by
holding the push button switch SW1 for 50 to 60 seconds.
This will reset all configuration settings and the EEPROM
back to the factory default settings. LED3 (green) will turn
off when entering reset configuration mode. Once LED3
(green) turns off, release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 (Source)
FP1 Selection – Low water coil temperature
limit setting for freeze detection. On = 30°F;
Off = 15°F.
SW2-2 (Load)
FP2 Selection – On = 30°F; Off = 15
°
F
SW2-3
RV – O/B - thermostat type. Heat pump
thermostats with “O” output in cooling or “B”
output in Heating can be selected. On = O; Off = B.
SW2-4
Access Relay Operation (P2)
and 2-5
Access Relay Operation
SW2-4
SW2-5
Cycle with Blower
n/a
Cycle with Compressor
OFF
OFF
Water Valve Slow Opening
ON
OFF
Cycle with Comm. T-stat Hum Cmd
n/a
Cycle with Blower
- (Not used on water-to-water)
Cycle with Compressor
- The accessory relay will cycle
with the compressor output.
Water Valve Slow Opening
- The accessory relay will
cycle and delay both the blower and compressor output
for 90 seconds.
SW2-6
CC Operation – selection of single or dual capacity
compressor. On = Single Stage; Off = Dual Capacity
SW2-7
Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and
ALM Outputs. On = Continuous; Off = Pulsed
SW2-8
Future Use
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By
cutting JW2, ALM becomes a dry contact connected to ALG.
Field Selectable Options via Software
(Selectable via the Aurora AID Tool)
Safety Features
The following safety features are provided to protect the
compressor, heat exchangers, wiring and other components
from damage caused by operation outside of design conditions.
Fuse
– a 3 amp automotive type plug-in fuse provides
protection against short circuit or overload conditions.
Anti-Short Cycle Protection
– 4 minute anti-short cycle
protection for the compressor.
Random Start
– 5 to 80 second random start upon power up.
The Aurora ‘Base’ Control System cont.