Step 10F – Set Relay 1 SETPOINT Time or Volume using
▲
or
▼
. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior
to activating the relay. The start of regeneration is defined as the first backwash cycle or Regenerant
Draw UP (1” only) or DN, whichever comes first. Ranges from 0 to 500 minutes.
• Relay Actuation Volume: Relay activates after a set number of liters have passed. Ranges from 1 to
200 liters.
Press NEXT to go to Step 11F. Press REGEN to return to previous step.
STEP 10F
Step 11F: Set Relay DURATION TIME using
▲
or
▼
.
• If TIME is selected in Step 9F, the relay will deactivate after the time set has expired. Ranges from
0:01 to 500:00 minutes.
• If Volume or REGEN Volume is selected in Step 9F, the relay will deactivate after the time set has
expired.
Press NEXT to go to Step 12F. Press REGEN to return to previous step.
STEP 11F
STEP 12F
Step 12F: Set Relay 2 operation using
▲
or
▼
. Set Relay 1 operation using
▲
or
▼
. The choices are:
• Set REGEN TIME: Relay activates after a set time at the beginning of a regeneration and then
deactivates after a set period of time. The start of regeneration is defined as the first backwash cycle or
Regenerant Draw UP (1” only) or DN, whichever comes first.
• Set VOLUME: Relay activates after a set number of liters have been used while in service and then
deactivates after a set period of time or after the meter stops registering flow, whichever comes first.
• Set REGEN VOLUME: Relay activates after a set number of liters have been used while in
service or during regeneration and then deactivates after a set period of time or after the meter stops
registering flow, whichever comes first.
• ERROR MONITOR: When Error Monitor is selected, Relay 2 closes whenever the valve enters the
Error Mode, and immediately deactivates when Error Mode is exited.
• If set to OFF or ERROR MONITOR, Steps 13F and 14F will not be shown.
Press NEXT to go to Step 13F. Press REGEN to return to previous step.
STEP 13F
Step 13F: Set Relay 2 SETPOINT Time or Volume using
▲
or
▼
. The choices are the same as Step
10F.
Press NEXT to go to Step 14F. Press REGEN to return to previous step.
STEP 14F
Step 14F: Set Relay DURATION TIME using
▲
or
▼
.
• If TIME is selected in Step 12F the relay will deactivate after the time set has expired.
• If Volume or REGEN Volume is selected in Step 12F the relay will deactivate after the time set has
expired or after the meter stops registering flow, whichever comes first.
Press NEXT to go to Step 15F. Press REGEN to return to previous step.
STEP 15F
Step 15F: Set Service Alarm using
▲
or
▼
. The choices are Time, m³, BOTH or OFF. Selecting OFF
disables this feature. If OFF is selected press NEXT to exit OEM System Setup. If TIME, m³ or BOTH
is selected press NEXT to select the TIME and/or m³ values. Press REGEN to return to previous step.
RETURN TO NORMAL MODE