CK and EQ Manual
Page 15
STEP 11S
Step 11S: Set Relay 1 SETPOINT Time or Volume using
▲
or
▼
. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior to activating
the relay. The start of regeneration is defined as the first backwash cycle or Regenerant Draw UP (1” only) or DN,
which ever comes first. Ranges from 0 to 500 minutes.
• Relay Actuation Volume: Relay activates after a set number of liters have passed. Ranges from 1 to 200 liters.
Press NEXT to go to Step 12S. Press REGEN to return to previous step.
STEP 12S
Step 12S: Set Relay DURATION TIME using
▲
or
▼
.
• If TIME is selected in Step 10S, the relay will deactivate after the time set has expired. Ranges from 0:01 to
500:00 minutes.
• If Volume or REGEN Volume is selected in Step 10S, the relay will deactivate after the time set has expired.
Press NEXT to go to Step 13S. Press REGEN to return to previous step.
Step 13S: Set Relay 2 operation using
▲
or
▼
. The choices are the same as Step 10S, with the addition of
Error Monitor. When Error Monitor is selected, Relay 2 closes whenever the valve enters the Error Mode, and
immediately deactivates when Error Mode is exited.
• If set to Off, Steps 14S and 15S will not be shown.
Press NEXT to go to Step 14S. Press REGEN to return to previous step.
STEP 13S
STEP 14S
Step 14S: Set Relay 2 SETPOINT Time or Volume using
▲
or
▼
. The choices are the same as Step 11S.
Press NEXT to go to Step 15S. Press REGEN to return to previous step.
STEP 15S
Step 15S: Set Relay DURATION TIME using
▲
or
▼
.
• If TIME is selected in Step 13S the relay will deactivate after the time set has expired.
• If Volume or REGEN Volume is selected in Step 13S the relay will deactivate after the time set has expired or
after the meter stops registering flow, whichever comes first.
Press NEXT to go to Step 16S. Press REGEN to return to previous step.
Step 16S: Set Service Alarm using
▲
or
▼
. The choices are Time, m³, BOTH or OFF. Selecting OFF disables
this feature. If OFF is selected press NEXT to exit OEM System Setup. If TIME, m³ or BOTH is selected press
NEXT to select the TIME and/or m³ values. Press REGEN to return to previous step.
STEP 16S
RETURN TO NORMAL MODE