background image

CK and EQ Manual

 

Page 15

STEP 11S

Step 11S: Set Relay 1 SETPOINT Time or Volume using 

 or 

. The choices are:

• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior to activating 

the relay. The start of regeneration is defined as the first backwash cycle or Regenerant Draw UP (1” only) or DN, 

which ever comes first. Ranges from 0 to 500 minutes. 

• Relay Actuation Volume: Relay activates after a set number of liters have passed. Ranges from 1 to 200 liters.

Press NEXT to go to Step 12S. Press REGEN to return to previous step.

STEP 12S

Step 12S: Set Relay DURATION TIME using 

 or 

• If TIME is selected in Step 10S, the relay will deactivate after the time set has expired. Ranges from 0:01 to 

500:00 minutes. 

• If Volume or REGEN Volume is selected in Step 10S, the relay will deactivate after the time set has expired. 

Press NEXT to go to Step 13S. Press REGEN to return to previous step.

Step 13S: Set Relay 2 operation using 

 or 

. The choices are the same as Step 10S, with the addition of 

Error Monitor. When Error Monitor is selected, Relay 2 closes whenever the valve enters the Error Mode, and 

immediately deactivates when Error Mode is exited.

• If set to Off, Steps 14S and 15S will not be shown. 

Press NEXT to go to Step 14S. Press REGEN to return to previous step.

STEP 13S

STEP 14S

Step 14S: Set Relay 2 SETPOINT Time or Volume using 

 or 

. The choices are the same as Step 11S.

Press NEXT to go to Step 15S. Press REGEN to return to previous step.

STEP 15S

Step 15S: Set Relay DURATION TIME using 

 or 

• If TIME is selected in Step 13S the relay will deactivate after the time set has expired. 

• If Volume or REGEN Volume is selected in Step 13S the relay will deactivate after the time set has expired or 

after the meter stops registering flow, whichever comes first. 

Press NEXT to go to Step 16S. Press REGEN to return to previous step.

Step 16S: Set Service Alarm using 

 or 

. The choices are Time, m³, BOTH or OFF. Selecting OFF disables 

this feature. If OFF is selected press NEXT to exit OEM System Setup. If TIME, m³ or BOTH is selected press 

NEXT to select the TIME and/or m³ values. Press REGEN to return to previous step.

STEP 16S

RETURN TO NORMAL MODE

Summary of Contents for CK

Page 1: ...Water Specialist CK and EQ Control Valve Programming and Cover Drawing Manual...

Page 2: ...Page 2 CK and EQ Manual...

Page 3: ...ver and Drive Assembly 4 OEM General Programming Instructions 5 OEM Cycle Sequence 7 OEM Softener System Setup 13 Setting Options Table 16 OEM Filter System Setup 17 Installer Display Settings 20 User...

Page 4: ...ect On Off Operation PC Board Relay Terminal Block Relay RLY 1 Coil V Coil RLY 2 Coil Relay Driver Output Type Dual Solid State 12VDC wet contacts N O Relay Driver Output Capacity 12VDC 100mA per rela...

Page 5: ...culated Yes Off Auto Yes If desired enter a value less than estimated capacity Yes Yes Yes Off Any Number Yes Yes Automatically calculated Yes Any Number Auto Yes Yes If desired enter a value less tha...

Page 6: ...he preset regeneration time For Valve Type 1 0T press and hold CLOCK and for about 3 seconds to initiate an exchange of the tank in Service without cycling the regeneration valve After tank switch day...

Page 7: ...lease Then press NEXT and simultaneously for 3 seconds and release If screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated To unlock press NEXT and CLOCK in sequence then...

Page 8: ...y Set System Capacity OEM Softener System Setup Step 8S Set to AUTO Set to AUTO OEM Softener System Setup Step 9S Set regeneration time option to IMMEDIATE REGEN Set regeneration time option to IMMEDI...

Page 9: ...e returned to Service until the error is corrected and reset Retracted Valve A in Service Position MAV piston rod Retracted Extended Valve B in Service Position MAV piston rod Extended Note Clack Twin...

Page 10: ...SOURCE Allows Auxiliary MAV to switch positions before the start of regeneration and then switch back at the end of regeneration Set OFF Deactivates this output Only use Clack Motorized Alternating V...

Page 11: ...sed for an accumulative time of 2 minutes a regeneration will occur at the scheduled delayed regeneration time In a twin alternating system once the dP switch is triggered the PC Board will display RE...

Page 12: ...r until Regenerant Draw DN appears Prior to selecting the upflow regeneration cycle verify that the correct body main piston regenerant piston and stack are being used and that the injector plug s are...

Page 13: ...s 1 to 480 STEP 1S Step 1S Press NEXT and simultaneously for 3 seconds and release If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated To unlock press NEXT and CLOCK i...

Page 14: ...ccur immediately when the volume capacity reaches 0 zero or BOTH means regeneration will occur at one of the following the preset time when the volume capacity falls below the reserve or the specified...

Page 15: ...s Step 10S with the addition of Error Monitor When Error Monitor is selected Relay 2 closes whenever the valve enters the Error Mode and immediately deactivates when Error Mode is exited If set to Off...

Page 16: ...ediately when volume capacity reaches 0 Time of regeneration will not be allowed to be set because regeneration will always occur when volume capacity reaches 0 Any number IMMEDIATE REGEN OFF Reserve...

Page 17: ...or 3 seconds and release Step 2F Choose FILTERING using or Press NEXT to go to Step 3F Press REGEN to exit OEM Filter System Setup Step 3F Select the time for the first cycle which in this example is...

Page 18: ...es of no water usage when the volume capacity reaches 0 zero DELAYED REGEN is the default if Step 4CS is set to VALVE A or VALVE B and BOTH will not be available IMMEDIATE REGEN is the default if Step...

Page 19: ...een used while in service and then deactivates after a set period of time or after the meter stops registering flow whichever comes first Set REGEN VOLUME Relay activates after a set number of liters...

Page 20: ...o return to previous step STEP 6I STEP 6I Next Regeneration Time hour Set the hour of day for regeneration using or The default time is 2 00 This display will show not to be viewed if IMMEDIATE is sel...

Page 21: ...system Contact information will be displayed if it was edited For concerns with phone number or banner text displays contact OEM for instructions The fifth display will show either DP or HOLD if the...

Page 22: ...the system calls for it usually referred to as manual regeneration There may be a period of heavy water usage because of guests or a heavy laundry day To initiate a manual regeneration at the preset d...

Page 23: ...icates the time of day should be reset and the non rechargeable battery replaced The system will remember the rest Error Message If the word ERROR and a number are displayed contact the OEM for help T...

Page 24: ...This display will equal zero if a water meter is not installed Press NEXT to go to Step 4D Press REGEN to return to previous step STEP 4D STEP 4D Reserve History Volume used for last 7 days If the val...

Page 25: ...ll active MAV drives Use or to review the history of all active MAV outputs TTT measured MAV drive time VVV measured MAV drive voltage CCC total number of drives in or out indicates piston drive into...

Page 26: ...s display shows the total number of regenerations that have occurred since startup Press NEXT to go to Step 5VH Press REGEN to return to previous step STEP 5VH STEP 5VH Volume total used since start u...

Page 27: ...each tank until the next regeneration Prior to selecting the upflow regeneration cycle verify that the correct body main piston regenerant piston and stack are being used and that the injector plug s...

Page 28: ...Page 28 CK and EQ Manual Form No V3435CK 6 16 2014 U S Patents 6 402 944 6 444 127 6 776 901 Translation supported by Pollet Water Group...

Reviews: