background image

 5.3. 

BCC Checksum

 

As a means of error detection, a block check character (BCC) checksum is added to the RS -485 communication function 

of the AM-215A panelmeter.    See the following illustrations for details on the transmission and reception formats.  

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

6.    Communication Commands

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

User’s Manual AM-215A Series RS-485

                                                                       3/8 

STX

D

S

P

ETX

A

E

CR

LF

Example of BCC Checksum for Transmission

Character

Hexadecimal

02H

44H

53H

50H

03H

41H

45H

0DH

0AH

BCC H = Higher-order 4 bits among the lower-order 8 bits of 
the sum of the hexadecimal values numbered from [1] to [4]
44H+53H+50H+03H=EAH

[1]

[2]

[3]

[4]

BCC L = Lower-order 4 bits among the lower-order 8 bits of 
the sum of the hexadecimal values numbered from [1] to [4]
44H+53H+50H+03H=EAH

Example of BCC Checksum for Reception

Character

STX

0

0

0

ETX

9

D

CR

LF

02H

30H

30H

30H

03H

39H

44H

0DH

0AH

[5]

[6]

[7]

[11]

20H

[1]

[2]

[3]

5

35H

[4]

20H

20H

H

48H

[8]

[9]

I

49H

[10]

20H

BCC L = Lower-order 4 bits among the lower-order 8 bits of the 

sum of the hexadecimal values numbered from [1] to [11]

20H+20H+20H+35H+30H+30H+30H+20H+48H+49H+03H=1D9H

BCC H = Higher-order 4 bits among the lower-order 8 bits of the 

sum of the hexadecimal values numbered from [1] to [11]

20H+20H+20H+35H+30H+30H+30H+20H+48H+49H+03H=1D9H

Function

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

Char.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Char.

Length

Length

D

S

P CR LF

3

5

0

0

0

H

I

CR LF

10

(+ reading, w/o decimal point)

-

5

0

0

0

H

I

CR LF

10

(- reading, w/o decimal point)

5

0

0

.

0

H

I

CR LF

11

(+ reading, w/ decimal point)

<

=

9

8

0

0

H

I

CR LF

10

(+ overrange reading, w/o decimal point)

<

=

-

9

8

0

.

0

H

I

CR LF

11

(- overrange reading, w/ decimal point)

Measured value response

M

E

S CR LF

3

0

CR LF

12

(+ reading, w/o decimal point)

0

.

0

1

CR LF

12

(+ reading, w/ decimal point)

-

1

CR LF

12

(- reading, w/o decimal point)

-

0

.

0

0

5

CR LF

12

(- reading, w/ decimal point)

<

=

9

8

0

.

5

CR LF

12

(+ overrange reading, w/ decimal point)

<

=

-

9

8

0

.

5

CR LF

12

(- overrange reading, w/ decimal point)
All responses are the fixed length of 12 characters.

Comparison results response

J

G

M CR LF

3

H

I

CR LF

15

(In HI, a judgment result is.)

G

O

CR LF

15

(In GO, a judgment result is.)

L

O

CR LF

15

(In LO, a judgment result is.)

H

.

H

I

CR LF

15

(In HH and HI, a judgment result is.)

L

O

.

L

L

CR LF

15

(In LO and LL, a judgment result is.)

Hold remote control response

S

T

H CR LF

3

S

T

A

R

T

CR LF

6

(Response with the status of the hold function being set to OFF
 by remote control)

H

O

L

D

CR LF

6

(Response with the status of the hold function being set to ON
by remote control)

Hold terminal response

E

S

A CR LF

3

S

T

A

R

T

CR LF

6

(Response with the status of the hold function being set to OFF)

H

O

L

D

CR LF

6

(Response with the status of the hold function being set to ON)

Hold remote control

S

T

H

S CR LF

5

Y

E

S

CR LF

5

(Sets the hold function to OFF.)

S

T

H

H CR LF

5

Y

E

S

CR LF

5

(Sets the hold function to ON.)

Trigger input

T CR LF

1

5

0

0

.

0

H

I

CR LF

11

(+ reading, w/ decimal point)
Note: The response is the same as that of “DSP”.

Hold remote control cancellation

E

S

M CR LF

3

Y

E

S

CR LF

5

Measured value and comparison
results response

Summary of Contents for AM-215A

Page 1: ...TOR ANALOG OUT or RS485 INPUT EXC POWER c e c e c e AL1 AL2 SET POINT COMPARATOR AM 215A INSTRUCTION MANUAL Caution 1 The equipment may be damaged if the input current or voltage exceeds the maximum...

Page 2: ...y When using a 2 wire sensor terminals 2 11 should be externally connected 4 When no terminals are selected for outputting do not connect anything to vacant terminals AL1 AL2 Condition data A group of...

Page 3: ...et The default value is 9999 The default value is 9999 A menu is displayed only the option output form 4 The default value is 0 A displayed value to obtain an output from the full scale side of the an...

Page 4: ...g temperature and humidity ranges 0 to 50 C 35 to 85 RH no condensation Storage temperature and humidity ranges 20 to 70 C 60 or lower RH no condensation Supply voltage DC 24 V 20 Consumed power Appro...

Page 5: ...inearity compensation of the rectifying point 2 is inputted The input value display value before linearity compensation of the rectifying point 16 is inputted The output value display value before lin...

Page 6: ...ransmission control procedure Signal name used Number of units that can be connected Transmission line length Delimiter Parity bit Start stop Two wire half duplex polling selecting 2400 4800 9600 1920...

Page 7: ...to ON AL1 AL2 AL1 AL2 AL1 AL2 AL1 AL2 Function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Char Length 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Char Length Establishment of...

Page 8: ...0 H I CR LF 10 reading w o decimal point 5 0 0 0 H I CR LF 11 reading w decimal point 9 8 0 0 H I CR LF 10 overrange reading w o decimal point 9 8 0 0 H I CR LF 11 overrange reading w decimal point M...

Page 9: ...3 Response with the status of the hold function being remote controlled D Z R CR LF 3 Response with the status of the digital zero function being remote controlled R L Y CR LF 3 Response with the sta...

Page 10: ...T 1 W 1 CR LF 14 Response with the status of the tracking zero time being 1 and tracking zero width being 1 T R K O N T 9 9 W 9 9 CR LF 16 Response with the status of the tracking zero time being 99 a...

Page 11: ...O side logic function being set to N C N CR LF 1 L L O N O CR LF 8 Response with the status of the LO side logic function being set to N O L L O N C CR LF 8 Response with the status of the LO side log...

Page 12: ...on correction data items being 16 Setting for number of linearization L N O 0 2 CR LF 6 Y E S CR LF 5 correction data items Sets the number of linearization correction data items to 02 L N O 1 6 CR LF...

Page 13: ...unication parameter failure Note Under normal conditions this response is made only once Note ERROR B to ERROR F are available as the response commands for acknowledgment Note If a response to the ERR...

Reviews: