Fig 14-5
Signal overview (Generating set)
14.2
Functions
14.2.1
Start
The engine has a pneumatic starting motor controlled by a solenoid valve. The solenoid valve
can be energized either locally with the start button, or from a remote control station. In an
emergency situation it is also possible to operate the valve manually.
Starting is blocked both pneumatically and electrically when the turning gear is engaged. Fuel
injection is blocked when the stop lever is in stop position (conventional fuel injection).
Startblockings are handled by the system on the engine (main control module).
14.2.1.1
Startblockings
Starting is inhibited by the following functions:
●
Turning gear engaged
●
Stop lever in stop position
●
Pre-lubricating pressure low
●
Local engine selector switch in blocked position
●
Stop or shutdown active
●
External start blocking 1 (e.g. reduction gear oil pressure)
●
External start blocking 2 (e.g. clutch position)
●
Engine running
For restarting of a diesel generator in a blackout situation, start blocking due to low
pre-lubricating oil pressure can be suppressed for 30 min.
14-6
Wärtsilä 26 Product Guide - a9 - 7 September 2016
Wärtsilä 26 Product Guide
14. Automation System
Summary of Contents for WARTSILA 26
Page 1: ...W RTSIL 26 PRODUCT GUIDE...
Page 12: ...This page intentionally left blank...
Page 34: ...This page intentionally left blank...
Page 50: ...This page intentionally left blank...
Page 92: ...This page intentionally left blank...
Page 114: ...This page intentionally left blank...
Page 148: ...This page intentionally left blank...
Page 160: ...This page intentionally left blank...
Page 172: ...This page intentionally left blank...
Page 182: ...This page intentionally left blank...
Page 188: ...This page intentionally left blank...
Page 190: ...This page intentionally left blank...
Page 193: ......
Page 194: ......
Page 195: ......