background image

South Bend, Indiana USA 

 |

  networketi.com

PT-SINGLE

 INSTALLATION MANUAL  |  PART NO. 

25166

 REV 

D

7

Power Fail. Critical alarms always turn off the heat, unless 

Fire Protect Mode is ON. To continue normal operation, 

any of these will require a manual reset. The manual reset 

(TEST/RESET BACK pushbutton) will start a self test, and 

if all Critical Alarms are cleared then normal operation 

will resume.

Non-critical Alarms can be Latching or Non-Latching 

depending on the Latching setting alarms and include 

Low Current, Low Temperature, High Temperature, 

and Sensor Fault. A Sensor Fault will stop temperature 

regulation (with heat on or off depending on the Fail 

Mode setting), but as soon as the sensor is corrected, 

then operation will immediately resume. The other Non-

critical Alarms do not inhibit operation.

Note:

 Latching alarms require manual clearing to resume 

operation. 

The Manual Self Test clears all alarms, checks Ground 

Fault Current, and checks Low Current if the Low Current 

delay is set to five seconds or less. The Auto Self Test does 

not clear alarms, but otherwise functions the same as the 

Manual Self Test.

PT-SINGLE

 Front Panel

Indicator Lights (See Figure 8.)

• POWER indicator – This green LED indicates that the

 

PT-SINGLE

 is receiving power.

• HEAT indicator – This yellow LED indicates when the

 

heater is energized.

• LOW TEMP indicator – This blue LED indicates when

 

sensors detect temperature has fallen below the Low

 

Temp Alarm threshold.

•  ALARM indicator – This red LED indicates when there is

 

high ground fault current detected or any other alarm

 

condition exists.

Note:

 Because the unit has no ON/OFF power switch, 

power runs to the unit as soon as facility power is 

connected to it. When the unit has power, the green 

POWER indicator will be lit.

CONTROLS AND SCREENS

CONTROLS

Pushbuttons

•  

UP and DOWN

 pushbuttons – These black pushbuttons

change the display and menu screens. They are also

used for changing settings or values within the menus.

•  

ENTER

 pushbutton – This green pushbutton is for

selecting and entering settings or values within the

menu.

•  

TEST/RESET BACK

 pushbutton – This red pushbutton

has the following functions:

–  To test the ground fault detector circuit itself AND

to test for a ground fault when the heat load is not

energized (the heater will energize during the test).

This will also test for Low Current if the Low Current

delay setting is set to 5 seconds or less. Note:

whenever the heat is on, the unit is continuously

checking for a ground fault.

–  To reset the system after a ground fault. If the ground

fault no longer exists, then normal operation will

resume.

– Clearing any other latched alarm conditions if the

alarm condition no longer exists.

FIGURE 8. 

PT-SINGLE

 front panel

UP

DOWN

ENTER

GPT 130

HEAT TRACE CONTROL

POWER

HEAT

LOW TEMP

ALARM

TEST / RESET

BACK

Summary of Contents for TRACON PT-SINGLE

Page 1: ...l Odor or Smoke In the event of smoke or a burning or abnormal odor immediately interruptpowertotheunitbyturningoff thecircuitbreakerprotecting the unit Electrical Shock Fire Hazard Any installation i...

Page 2: ...nection The internal load contactor is rated to South Bend Indiana USA networketi com switch up to 30 A resistive The Integral GFEP provides safety in compliance with national and local electrical cod...

Page 3: ...e only Listed Type 4X IP66 liquid tight conduit hubs or cable glands Connect the hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cab...

Page 4: ...PST contacts rated for heater loads up to 30 A ac and 277 V ac These two contacts are used to control both legs of the input power Line and Neutral Manual Load Test To manually energize the load selec...

Page 5: ...to 230 F 40 C to 110 C See Figure 5 for proper wiring when using a thermistor sensor RTD The unit can use an RTD sensor for applications requiring a wider temperature range The PT SINGLE can operate...

Page 6: ...contact to open to signal an alarm or power off condition then connect the other alarm relay lead to the NO Normally Open terminal If the unit has power and there are no alarm conditions then the NO...

Page 7: ...en the heater is energized LOW TEMP indicator This blue LED indicates when sensors detect temperature has fallen below the Low Temp Alarm threshold ALARM indicator This red LED indicates when there is...

Page 8: ...Load Current alarm you must view the Load Current Display screen Note If the heater relay is off the ground fault number is NOT shown Temperature Display screen Indicates the current temperature in Fa...

Page 9: ...eens that display multiple fields there are two columns The left column displays the name of the parameter and the right column displays the current value Initially one of the fields in the left colum...

Page 10: ...South Bend Indiana USA networketi com PT SINGLE INSTALLATION MANUAL PART NO 25166 REV D 10 FIGURE 10 Setting screen sequence...

Page 11: ...High temperature alarm delay 0 s to 3000 s Default 300 s Low current alarm threshold 0 0 A to 10 0 A Default 0 1 A Enabled Low current alarm delay 0 s to 300 s Default 5 s Enabled High current alarm t...

Page 12: ...to mark the Return Merchandise Authorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about...

Reviews: