PT-SINGLE

 INSTALLATION MANUAL  |  PART NO. 

25166

 REV 

D

11

SPECIFICATIONS

General

Certifications 

UL 60730–1, UL 1053,  

CSA E60730–1:13

Environmental

Area of use 

Nonhazardous locations

Operating temperature range 

−40 °F to 131 °F (−40 °C to 55 °C)

Enclosure

Dimensions 

8 1/8” (W) x 5 1/2” (H) x 4 3/8” (D) 207 

mm (W) x 140 mm (H) x  

112 mm (D)

Ingress protection 

NEMA 4X, IP66

Cover attachment 

Polycarbonate cover, plastic screws

Cable entries 

Two liquid–tight cable glands installed 

for sensor and alarm leads, cable 

diameter 0.08” to 0.24” (2 mm to 6 

mm) One 1.046” hole to accommodate 

a ¾” conduit fitting for power wiring 

connection

Material 

Polycarbonate

Weight 

2.7 lb. (1.22 kg)

Mounting 

Wall mount with flanges

Wiring Terminal Ratings

Power 

Barrier Strip Terminals for Line, Neutral, 

and Ground; use 10 AWG wires rated 

for at least 194 °F (90 °C)

Sensors 

Terminal Block, rising cage clamp, 

12–28 AWG leads

Alarm 

relay Terminal Block, rising cage clamp, 

12–28 AWG leads

Parameter Settings

Temperature setpoint heat ON 

Adjustable −99.9 °F to 999 °F (−73.3 

°C to 537.7 °C) Default 38 °F (3.33 °C)

Temperature setpoint heat OFF

Adjustable −99.9 °F to 999 °F (−73.3 

°C to 537.7 °C) Default 40 °F (4.44 °C)

Low–temperature alarm 

threshold 

−99.9 °F to 999 °F (−73.3 °C to 537.7 

°C) Default 35 °F (−1.7 °C) Disabled

Low–temperature alarm delay 

0 s to 3000 s Default 300 s

High–temperature alarm 

threshold 

−99.9 °F to 999 °F (−73.3 °C to 537.7 

°C) Default 140 °F (60 °C) Disabled

High–temperature alarm delay  0 s to 3000 s Default 300 s
Low–current alarm threshold 

0.0 A to 10.0 A Default 0.1 A Enabled

Low–current alarm delay 

0 s to 300 s Default 5 s Enabled

High–current alarm threshold 

0.0 A to 55.0 A Default 30.0 A Disabled

High–current alarm delay 

0 s to 600 s Default 300 s

Ground fault limit current 

1.0 mA to 300.0 mA Default 30 mA

Self–Test Interval 

1 h to 250 h Default 24 h Enabled

Temperature Unit 

°F or °C Default °F

User Interfaces

Pushbuttons 

UP, DOWN, ENTER, TEST / RESET 

BACK

DIP switches 

RTD wiring configuration Panel 

lockout

Remote Interface

Alarm relay 

Isolated SPDT 1 AMP Class 2 

contact

Indicators

Status indicator 

Power (Green) Heater (Yellow) Low 

Temperature (Blue) Summary alarm 

(Red)

Display 

2.7” OLED graphic 128x64

Summary alarm relay reporting 

Low temperature High temperature 

Low load current High load current 

High ground fault current Stuck 

relay Sensor fault Internal fault

Control Ratings

Temperature accuracy 

+/− 2 °F (1 °C)

Temperature Sensors

Temperature inputs 

(Included) Thermistor: 100k ohms 

at 25 °C, range −40 °F to 230 

°F (−40 °C to 110 °C), 20ft Lead 

(25076) RTD Sensor: Platinum, 

Alpha = 0.00385, ITS–90,100 ohms 

GFEP (Ground–Fault 

Equipment Protection)

Operation 

Continuously tests ground fault 

current whenever the load is on; 

also manually and periodically tests 

equipment ground fault current 

with each self–test.

Range 

Adjustable 1 mA to 300 mA, 

Default 30 mA

Automatic self–test 

Verifies GFEP functionality every 

24 hr. and whenever the load is 

energized

Power

Supply voltage 

100 – 277 V ac 50/60 Hz

Controller power consumption 

5 W maximum, 2 W idle

Load rating 

30 A, 100 – 277 V ac resistive

Summary of Contents for TRACON PT-SINGLE

Page 1: ...l Odor or Smoke In the event of smoke or a burning or abnormal odor immediately interruptpowertotheunitbyturningoff thecircuitbreakerprotecting the unit Electrical Shock Fire Hazard Any installation i...

Page 2: ...nection The internal load contactor is rated to South Bend Indiana USA networketi com switch up to 30 A resistive The Integral GFEP provides safety in compliance with national and local electrical cod...

Page 3: ...e only Listed Type 4X IP66 liquid tight conduit hubs or cable glands Connect the hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cab...

Page 4: ...PST contacts rated for heater loads up to 30 A ac and 277 V ac These two contacts are used to control both legs of the input power Line and Neutral Manual Load Test To manually energize the load selec...

Page 5: ...to 230 F 40 C to 110 C See Figure 5 for proper wiring when using a thermistor sensor RTD The unit can use an RTD sensor for applications requiring a wider temperature range The PT SINGLE can operate...

Page 6: ...contact to open to signal an alarm or power off condition then connect the other alarm relay lead to the NO Normally Open terminal If the unit has power and there are no alarm conditions then the NO...

Page 7: ...en the heater is energized LOW TEMP indicator This blue LED indicates when sensors detect temperature has fallen below the Low Temp Alarm threshold ALARM indicator This red LED indicates when there is...

Page 8: ...Load Current alarm you must view the Load Current Display screen Note If the heater relay is off the ground fault number is NOT shown Temperature Display screen Indicates the current temperature in Fa...

Page 9: ...eens that display multiple fields there are two columns The left column displays the name of the parameter and the right column displays the current value Initially one of the fields in the left colum...

Page 10: ...South Bend Indiana USA networketi com PT SINGLE INSTALLATION MANUAL PART NO 25166 REV D 10 FIGURE 10 Setting screen sequence...

Page 11: ...High temperature alarm delay 0 s to 3000 s Default 300 s Low current alarm threshold 0 0 A to 10 0 A Default 0 1 A Enabled Low current alarm delay 0 s to 300 s Default 5 s Enabled High current alarm t...