background image

South Bend, Indiana USA 

 |

  networketi.com

PT-SINGLE

 INSTALLATION MANUAL  |  PART NO. 

25166

 REV 

D

8

– On settings menus this pushbutton backs out of an 

operation without changing anything.

–  Energizes heater for system testing or troubleshooting. 

Pressing  this  pushbutton  for  five  seconds  while  on 

the Edit Settings screen will energize the heater for 

five minutes. Pressing the pushbutton again will de-

energize  the  heater  and  resume  normal  operation. 

The user can change screens while the test is in 

progress.

MAIN SCREENS

There are five main screens that can be accessed using 

the UP and DOWN pushbuttons. These screens cycle in 

the sequence shown in Figure 9; pressing UP or DOWN 

five times returns you to your starting position.

Note:

 After initial use the default display screen when 

left alone will be the last main screen that was displayed 

for more than five seconds.

Triple Display screen

  –  Displays  the  three  data  fields 

(Temperature, Load Current, Ground Fault Current) are 

all shown on this same screen. If there is an alarm, the 

field description will alternate with an alarm notification. 

In most cases, the alarm on this screen will identify 

what the alarm is, except for a Load Current alarm. To 

determine whether the Load Current alarm is a high or 

low Load Current alarm you must view the Load Current 

Display screen.

Note:

 If the heater relay is off, the ground fault number 

is NOT shown.

Temperature Display screen

 – Indicates the current 

temperature in Fahrenheit or Celsius. This screen will also

show any associated alarm conditions.

Load Current Display screen

 – Indicates the load current 

to the heaters in amps. This screen will also show any

associated alarm conditions.

Ground–Fault Current Display screen

 – Indicates the 

ground fault current in milliamps. This screen will also 

show any associated alarm conditions.

Note:

 If the heater relay is off, NO NUMBER IS SHOWN.

Note:

 In any of the main sequence screens, pressing 

the TEST/RESET BACK pushbutton will clear all latched 

alarms and perform a self–test, including a ground fault 

current test. The “Passed” or “Failed” result of the self–

test is then displayed, then returns to the default screen.

Settings screen

 – Allows access to all the parameter 

settings. The top line will say “Edit Settings” or “View 

Settings”, depending on whether the Panel Lockout 

function is set with the internal DIP switch (see page 7). 

With Panel Lockout enabled, most configuration settings 

can only be viewed, not edited. The only exception is the 

choice of Celsius or Fahrenheit temperature units.

Note:

 The GPT reads the Lock DIP switch position when 

the Settings screen is entered. If the switch is changed, 

you need to re-enter the Settings screen.

FIGURE 9. Main screen sequence

Summary of Contents for TRACON PT-SINGLE

Page 1: ...l Odor or Smoke In the event of smoke or a burning or abnormal odor immediately interruptpowertotheunitbyturningoff thecircuitbreakerprotecting the unit Electrical Shock Fire Hazard Any installation i...

Page 2: ...nection The internal load contactor is rated to South Bend Indiana USA networketi com switch up to 30 A resistive The Integral GFEP provides safety in compliance with national and local electrical cod...

Page 3: ...e only Listed Type 4X IP66 liquid tight conduit hubs or cable glands Connect the hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cab...

Page 4: ...PST contacts rated for heater loads up to 30 A ac and 277 V ac These two contacts are used to control both legs of the input power Line and Neutral Manual Load Test To manually energize the load selec...

Page 5: ...to 230 F 40 C to 110 C See Figure 5 for proper wiring when using a thermistor sensor RTD The unit can use an RTD sensor for applications requiring a wider temperature range The PT SINGLE can operate...

Page 6: ...contact to open to signal an alarm or power off condition then connect the other alarm relay lead to the NO Normally Open terminal If the unit has power and there are no alarm conditions then the NO...

Page 7: ...en the heater is energized LOW TEMP indicator This blue LED indicates when sensors detect temperature has fallen below the Low Temp Alarm threshold ALARM indicator This red LED indicates when there is...

Page 8: ...Load Current alarm you must view the Load Current Display screen Note If the heater relay is off the ground fault number is NOT shown Temperature Display screen Indicates the current temperature in Fa...

Page 9: ...eens that display multiple fields there are two columns The left column displays the name of the parameter and the right column displays the current value Initially one of the fields in the left colum...

Page 10: ...South Bend Indiana USA networketi com PT SINGLE INSTALLATION MANUAL PART NO 25166 REV D 10 FIGURE 10 Setting screen sequence...

Page 11: ...High temperature alarm delay 0 s to 3000 s Default 300 s Low current alarm threshold 0 0 A to 10 0 A Default 0 1 A Enabled Low current alarm delay 0 s to 300 s Default 5 s Enabled High current alarm t...

Page 12: ...to mark the Return Merchandise Authorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about...

Reviews: