PT-SINGLE

 INSTALLATION MANUAL  |  PART NO. 

25166

 REV 

D

5

TEMPERATURE SENSOR

The 

PT-SINGLE

 can use either a thermistor (provided), 

or a 3–wire RTD sensor. 

Thermistor (25076)

The 

PT-SINGLE

 comes with a thermistor temperature 

sensor with a 20 ft. jacketed cable that has an operating 

range 

of −40 °F to 230 °F (−40 ˚C to 110 ˚C). See Figure 

5 for 

proper wiring when using a thermistor sensor.

RTD

The unit can use an RTD sensor for applications 

requiring a wider temperature range. The 

PT-SINGLE

 

can operate with 3–wire RTD sensors. See Figure 5 for 

proper wiring 

and DIP switch configurations when 

using a 3–wire RTD 

sensor.

Note:

 The sensor must be selected in the Sensor Type 

parameter setting screen also.

FIGURE 5. Temperature sensor wiring and DIP switch configurations

The Thermistor input is not affected

by the DIP Switches

Summary of Contents for TRACON PT-SINGLE

Page 1: ...l Odor or Smoke In the event of smoke or a burning or abnormal odor immediately interruptpowertotheunitbyturningoff thecircuitbreakerprotecting the unit Electrical Shock Fire Hazard Any installation i...

Page 2: ...nection The internal load contactor is rated to South Bend Indiana USA networketi com switch up to 30 A resistive The Integral GFEP provides safety in compliance with national and local electrical cod...

Page 3: ...e only Listed Type 4X IP66 liquid tight conduit hubs or cable glands Connect the hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cab...

Page 4: ...PST contacts rated for heater loads up to 30 A ac and 277 V ac These two contacts are used to control both legs of the input power Line and Neutral Manual Load Test To manually energize the load selec...

Page 5: ...to 230 F 40 C to 110 C See Figure 5 for proper wiring when using a thermistor sensor RTD The unit can use an RTD sensor for applications requiring a wider temperature range The PT SINGLE can operate...

Page 6: ...contact to open to signal an alarm or power off condition then connect the other alarm relay lead to the NO Normally Open terminal If the unit has power and there are no alarm conditions then the NO...

Page 7: ...en the heater is energized LOW TEMP indicator This blue LED indicates when sensors detect temperature has fallen below the Low Temp Alarm threshold ALARM indicator This red LED indicates when there is...

Page 8: ...Load Current alarm you must view the Load Current Display screen Note If the heater relay is off the ground fault number is NOT shown Temperature Display screen Indicates the current temperature in Fa...

Page 9: ...eens that display multiple fields there are two columns The left column displays the name of the parameter and the right column displays the current value Initially one of the fields in the left colum...

Page 10: ...South Bend Indiana USA networketi com PT SINGLE INSTALLATION MANUAL PART NO 25166 REV D 10 FIGURE 10 Setting screen sequence...

Page 11: ...High temperature alarm delay 0 s to 3000 s Default 300 s Low current alarm threshold 0 0 A to 10 0 A Default 0 1 A Enabled Low current alarm delay 0 s to 300 s Default 5 s Enabled High current alarm t...

Page 12: ...to mark the Return Merchandise Authorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about...

Reviews: