background image

Error 

Code

Error

Fault

Possible Cause

Solution(s)

E 01

Exhaust gas Thermostat (boiler 

with open combustion) intervention

The boiler does not operate, 

E01 error code blinks

> Exhaust gas sensor fault

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

E 02

Water pressure in the system is 

low/system parameters are set 

incorrectly

The boiler does not operate, 

E02 error code blinks

> Water pressure in the 

boiler is not sufficient

> TsP parameter is set 

incorrectly

1-) Fill the boiler up to 1,2-1,5 bar as specified in the manual, 

the problem will be automatically solved.

2-) Check if the system pressure is 1,2-1,5 bar from the 

manometer on the lower right side of the boiler

3-) Call Authorized service if the fault remains unsolved

4-) Restart the boiler by pushing RESET button.

E 03

High water pressure in the system

The boiler does not operate, 

E01 error code blinks

>Water pressure in the 

system is higher than 3,8 

bars

1-) Drain the boiler down to 1,2-1,5 bar as specified in the 

manual, the problem will be automatically solved

2-) Check if the system pressure is 1,2-1,5 bar from the 

manometer on the lower right side of the boiler

3-) Call Authorized service if the fault remains unsolved.

4-) Restart the boiler by pushing RESET button.

E 04

Hot Domestic Water temperature 

sensor is faulty

The boiler does not operate 

in Hot Domestic Water mode, 

but operate in Heating system 

mode, E04 Error Code blinks 

on the display

> Hot Domestic Water 

temperature sensor is 

faulty

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

E 05

Heating system supply 

temperature sensor is faulty

The boiler does not operate, 

E05 error code blinks

> Heating system supply 

temperature sensor is 

faulty

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

E 06

No ignition

The boiler does not operate, 

E06 error code blinks

> Gas Supply fault

1-) First restart the boiler by pushing RESET button, and check 

if problem is solved

2-) Check if other appliances burning gas are operating. 

3-) Check if the main gas valve is open.

4-) Check if the boiler gas valve under the boiler is open.

5-) Restart the boiler by pushing RESET button, and check if 

problem is solved.

6-) Call the authorized service if not solved.

E 07

Safety Thermostat intervention

The boiler does not operate, 

E07 error code blinks

> Insufficient water in the 

system

> Pump clogging

> Pump Failure

> Pump Equipment 

clogging

1-) First restart the boiler by pushing RESET button, and check 

if problem is solved

2-) Check if the boiler heating system valves are open, if not, 

open all of them.

3-) Check if all radiator valves are open, if not open, minimum 

3 meter-radiators must be on.

4-) Restart the boiler by pushing RESET button, and check if 

problem is solved.

5-) Call the authorized service if not solved.

E 08

Flame circuit fault

False flame signal from burner 

or electrode

> Wearing or corrosion of 

electrode

> Electrode position

> Interruption on cable

> Water clogging in water 

flow pipe

> Electronic card

1-) Restart the boiler by pushing RESET button.

2-) Call the authorized service if fault remains unsolved.

E 09

No water circulation in the system

The boiler does not operate, 

E09 error code blinks

> Insufficient water in the 

system,

> Pump clogging,

> Pump Failure,

> Pump Equipment 

clogging

1-) Restart the boiler by pushing RESET button, and check if 

problem is solved.

2-) Check if the boiler heating system valves are open, if not, 

open all of them.

3-) Check if all radiator valves are open, if not open, minimum 

3 meter-radiators must be on

4-) Restart the boiler by pushing RESET button and check if 

the problem is solved

E 10

Heating temperature RETURN 

sensor is faulty

The boiler does not operate, 

E10 error code blinks

> Heating system RETURN 

temperature sensor is 

faulty

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

E 11

Gas valve modulator is not 

connected

The boiler does not operate, 

E11 error code blinks

> Gas valve line

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

E 12

Hot Domestic Water temperature 

fault in summer mode

The boiler does not operate, 

E12 error code blinks

> Hot Domestic Water 

temperature sensor in the 

boiler is faulty

1-) Restart the boiler by pushing RESET button. 

2-) Call the authorized service if fault remains unsolved.

(P40) Heating ignition delay time.

The boiler appliance is equipped with an electronic timer in order to 

prevent frequent ignition of the boiler. This time is set as 2 minutes as 

default, and it can be extended up to 10 minutes.

(P42) Ready Hot Water (Preheat enabled/disabled).

This function heats up the boiler and keep water hot in order to 

prepare your Hot Domestic Water request immediately as well as to 

reduce cold water consumption while waiting. This function can be 

enable or disable on 6-button Viwa 50 &

Viwa 65 models. Preheat function is enabled when hot water 

temperature increasing RESET button is pushed until the cycle is 

completed. Pre-On or Pre-Off is displayed on the LCD display for 5 

seconds at the end of this time.

 

Activation of this function in Viwa 50 & Viwa 65 models is carried out 

by our Authorized Service with parameter setting upon your request.

26

Summary of Contents for VIWA 50

Page 1: ...WALL MOUNTED CONDENSING BOILERS INSTALLATION USER MANUAL VIWA50 VIWA65...

Page 2: ...Viwa 50 Viwa 65...

Page 3: ...5 Use Of Split Flue Type Hermetic 2 2 16 Installation At Partially Protected Outsides 2 2 17 Electrical Connections 2 2 18 Optional Controls Room Thermostat Outside Temperature Sensor And Others 2 3 H...

Page 4: ...ed boiler Only APPROVED ORIGINAL spare parts should be used Bolts sealed with paint strictly forbidden to open The boiler must not be used by children younger 8 years or invalid persons without superv...

Page 5: ...Lawa Plus 150 11 606 000001 0 3 mm 30 120 mm 0 2 mm 6 30 mm mza E B NER TA DEM R Logo Kodu Aksi belirtilmeyen genel tolerans i in ISO 2768 M ge erlidir 0 8mm 400 1000 mm 0 5mm 120 400 mm 0 125 mm 3 6...

Page 6: ...r G25 Not Approved Approved Approved Not Approved BE FR YES I 2L Natural Gas 25 mbar G25 Not Approved Approved Approved Not Approved NL YES I 2ELL Natural Gas 20 mbar G20 Not Approved Approved Approve...

Page 7: ...boiler is to be mounted over the kitchen countertop or kitchen set there shall be a minimum 50 cm distance under the boiler Due to possibility of water draining from the Safety Valve of the boiler aft...

Page 8: ...e carefully controlled and will impact the boiler strength Ensure that gas valve connection is correct Flammable gas supply pipe should be able to supply correct adequate gas amount to the boiler when...

Page 9: ...and is thoroughly vented Check that the circulating pump is not jammed Purge the system bleeding off the air present in the gas pipe by operating the pressure relief valve on the gas valve inlet 2 1...

Page 10: ...esh Air Intake with Split Flue Sets Air Exhaust Gas B23 C13 Figure 10 Hermetic Concentric and Flue Split Flue type 2 1 10 Peripheral Distances of the Flue Outlet Connections For positioning of the flu...

Page 11: ...m 32 C at mid level 1 5 m above the floor level 40 C at ceiling level 0 100 mm from ceiling When installed as a class B appliance open flued not roomed sealed Installed in a room High level within 15...

Page 12: ...pe shall be secured with dowels and bracelets with 3 meter intervals 1 90 bend 2 Sealing ring 3 Sealing ring 4 Centering wire 5 External flue pipe 6 Inner wall flange 7 Outer wall flange 8 External fl...

Page 13: ...end equivalent length L5 1 0 m L6 2 0 m L Total 6 3 m 6 3 m Lmax 11 m It is correct in implementation Implementation L1 0 5 m L2 1 0 m 90 bend equivalent length L3 1 5 m L4 1 0 m 90 bend equivalent le...

Page 14: ...e L 500 mm 153 11 660 600026 80 125 Extension Flue L 1000 mm 153 11 660 600027 80 125 Extension Flue L 1500 mm 153 11 660 600028 80 125 Extension Flue L 2000 mm 153 11 660 600029 80 125 Bend 45 153 11...

Page 15: ...individual in accordance with directives and standards in force in the country where the boiler is installed Also ensure that the electricity installation complies with the maximum power to be supplie...

Page 16: ...r drainage of water into to the installation place when the safety valve is enabled 2 2 3 Drainage of the Condensate Water The appliance shall be connected to the drainage water network through pipes...

Page 17: ...drainage pipe outlet Open air flusher Figure 32 Outside Connection of Condensate Water Drainage Pipe SECTION 2 INS Outdoor flusher Condensate Water Drainage Pump Refer to detailed instructions of the...

Page 18: ...te exchanger at least one expansion tank must be placed in the return line of the cascade side and the return line of the heating system side Filter elements strainers must be fitted to return line of...

Page 19: ...ection 3 x 1 0 mm 2 2 Boiler Slave 1 Boiler Master 6 Boiler Slave INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4 Gas Filter 5 Vibration Isolator 6 Condensate Water Siphon a...

Page 20: ...s and eventual copies The content of this document is Bertelli Partners s r l s property You must not be copy or use it in whole or in part without a prior written consent by Bertelli Partn 0 MLC27 1...

Page 21: ...ture Sensor with Cable It is the sensor that notifies the maximum flow water temperature by measuring the outside air temperature It is necessary to use one for fuel economy in single boiler or cascad...

Page 22: ...ler heating and domestic hot water Leave the boiler in Stand by OFF on the display position thus Anti Frost Function will be enabled Turn off the boiler during maintenance and repair operations near t...

Page 23: ...oiler operates only for domestic hot water in this mode if a boiler is fitted To switch to domestic water position 3 2 4 Resetting the Boiler Restart When the appliance shows fault blocking error push...

Page 24: ...set with no 7 and 8 buttons and this temperature is shown on this display with no 10 indicator for Heating system and no 12 indicator for Hot Domestic Water Turning off the Boiler To turn off the boil...

Page 25: ...to the curves given below After connecting the Outside Temperature Sensor by means of the P04 parameter It is adjusted according to average outside temperature of your province This setting will be p...

Page 26: ...ton and check if problem is solved 2 Check if the boiler heating system valves are open if not open all of them 3 Check if all radiator valves are open if not open minimum 3 meter radiators must be on...

Page 27: ...ed 2 Check if the boiler heating system valves are open if not open all of them 3 Check if all radiator valves are open if not open minimum 3 meter radiators must be on 4 Restart the boiler by pushing...

Page 28: ...e authorized service if fault remains unsolved E 79 Minimum regulating current value is reached The boiler does not operate E79 error code blinks Gas Supply Pressure Wearing or corrosion of electrode...

Page 29: ...ode position Burning calibration Gas valve fault Electronic board 1 Call the authorized service first 2 Check for false flue OR flue gas clogging 3 Restart the boiler by pushing RESET button 2 Call Au...

Page 30: ...TION FOR GUARANTEE CONDITIONS This warranty provided by WARMHAUS does not include fixing or eliminating faults caused by use of the appliance for purposes other than intended use as well as the condit...

Page 31: ...n max C 25 47 25 47 Operating Pressure Maximum bar 4 4 Operating Pressure Minimum bar 0 5 0 5 Temperature Setting Range Temperature Setting Range C 35 60 35 60 Electrical Circuit Power Supply V AC 50...

Page 32: ...t and high temperature regime 2 4 88 87 8 Useful efficiency at 30 of rated heat output and low temperature regime 1 1 97 11 97 39 Auxiliary Electricity Consumption Full load elmax kW 0 09 0 10 Part lo...

Page 33: ...IP X5D GC NO Gas Categories G20 Maximum heat input Qn kW 50 Minimum heat input Qn kW 6 5 t 80 60 Maximum heat output Pn kW 48 7 Minimum heat output Pn kW 5 69 B 23 C 13 C 33 C 53 C 63 C 83 I2H I2E I2E...

Page 34: ...s IP X5D GC NO Gas Categories G20 Maximum heat input Qn kW 65 Minimum heat input Qn kW 8 t 50 30 Maximum heat output Pn kW 63 2 Minimum heat output Pn kW 7 29 B 23 C 13 C 33 C 53 C 63 C 83 I2H I2E I2E...

Page 35: ...50 61 Viwa 50 65 58 Viwa 65 35 35...

Page 36: ...VIWA50 VIWA65 WALL MOUNTED CONDENSING BOILERS INSTALLATION AND USER MANUAL VIWA 50 VIWA 65 Montaj Kullan m K lavuzu kodu 150 11 606 000037 Revizyon numaras R02 05 10 2018...

Reviews: