3.13. PLUME DISPLACEMENT KITS Ø60 MM
153.11.660.6000 31
Elbow( 87 ), Plume
87
153.11.660.6000 32
45
153.11.660.6000 33
87
153.11.660.6000 34
153.11.660.6000 35
153.11.660.6000 36
Product Name
Specification
Product Code
3.14. RECOMMENDATIONS OF PLUME KIT INSTALLATION
NOTE: Due to the nature of the boiler a plume of water vapour will be
discharged from the flue. This should be taken into account when siting
the flue terminal.
1. The following guidelines indicate the general requirements for siting
balanced flue terminals. For GB recommendations are given in BS 5440
Pt 1. For IE recommendations are given in the current edition of I.S. 813
“Domestic Gas Installations”.
2. If the terminal discharges onto a pathway or passageway, check that
combustion products will not cause a nuisance and that the terminal will
not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above ground or above
a flat roof to which people have access, then a suitable terminal guard
must be provided.
4. *Reduction to the boundary is possible down to 25 mm but the Plume
Displacement Kit Bend (45°) (part no. 153.11.660.6000 33) must be fitted.
Opening Window
or Door
150 mm
MIN.
Plume
Displacement Kit
Air Inlet
IMPORTANT:
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and nuisance - free
dispersal of combustion products.
IMPORTANT:
If fitting a Plume Displacement Flue Kit, the air inlet
must be a minimum of 150mm from any opening windows or
doors)