34
warmhaus.com
Transparent Parameters Menu (TSP)
Designation :
All Warmhaus Wallhung Boilers
Object
Type-model(s)
Burner Control Transparent Parameter List
Parameter no.
Parameter
Value Field
MINERWA 25
Default
P50
Relay configuration 1 LC27
0 – 8
0
0 = Not used
1 = Remote alarm normally open
2 = Remote alarm normally close
3 = Zone valve
4 = Automatic refill valve
5 = Not used
6 = Recirculation pump
7 = Zone valve with OT
8 = Not used
P51
Relay configuration 1 LC27
0 – 8
0
0 = Not used
1 = Remote alarm normally open
2 = Remote alarm normally close
3 = Zone valve
4 = Automatic refill valve
5 = Not used
6 = Recirculation pump
7 = Zone valve with OT
8 = Not used
P52
Automatic water refill
0 – 1
0
0 = Not present
1 = Present
P53
Parameter perc combustion
0 – 30
N/A
P54
Fluxmeter value for DHW request activation ( = value / 10 ( liter / minute)
10-40 / 10 (lt/min)
15
P55
DHW post ventilation time (value 1 = 10 seconds)
1 - 30 sec x 10
3
P56
DHW post circulation time ( value 1 = 1 second )
0 – 100
30
P57
Flue clapet configuration
0% – 10%
0
P58
Offset fan ignition phase
0 – 20
N/A
P59
Offset Fan Low NOx
0 – 40
N/A
P60
Offset CH turning off after ignition
0 – 20
0
P61
Exhaust temperature alarm ( C° )
20 C° – 150 C°
105
P62
Low Noise (B&P parameter)
0 – 1
0
Please CUT OFF the GAS to change this parameter
P63
Delay in zone valve activation ( value 1 = 10 seconds )
0 – 99
0