24
warmhaus.com
Failure
Code
Description of the Error
Malfunction
Probable Cause
Solution(s)
E 77
Absolute current values
reached
Boiler does not work, E77
error code flashing on the
screen
> Gas inlet pressure
> Aging or rust on the
electrode
> Recirculation on fluegas
path
> Blokage on flue or wrong
flue
> Electrode position
> Cabeling disconnections
> Combustion calibration
> Electronic board
> Gas valve failiure
1-) Call for authorised service at first
2-) Check gas supply pressure must be 20-17 mBar. Gas pressure must
be in between on this values while boiler on operational
3-) Check wrong flue OR flue gas blockage
4-) Check recirculation ( flue gas leak ) from flue gas path to fresh air
side, check flue gas sealings specially
5-) Check any problems on the ionisation electrode, (like condensation,
rust etc.), and control poistioning of the electrode, if electrode poistion
wrong calibrate electrode according to user manual page 118 or 119
6-) Check if the heat exchanger coils clogged or not
7-) Check for condensation on the cabling AND/OR on board
8-) Check earth connection between board and electrode
9-) Check electrode cabeling between board and electrode
10-) Check combustion CO2 or O2 values on HI and LO mode at
sweeper mode according to direction of manual page 67- 70
11-) Perform Auto Calibration according to page 76 or 77
12-) If fault still persists Replace board, but use original service key
from the board dismantled to keep original parameters and calibration
points. If original service key not used aslo adjust P15 releated to the
default value of boiler power and perform Au-To calibration according
to page 76 or 77
13-) if not successfull replace gas valve, and Perform Au-To calibration
according to page 76 or 77
Attention: Only authorised service must perform Au-To
calibration
E 78
Max regulation current value
reached
Boiler does not work, E78
error code flashing on the
screen
> Gas inlet pressure
> Aging or rust on the
electrode
> Recirculation on fluegas
path
> Blokage on flue or wrong
flue
> Electrode position
> Cabeling disconnections
> Combustion calibration
> Electronic board
> Gas valve failiure
1-) Call for authorised service at first
E 79
Min regulation current value
reached
Boiler does not work, E79
error code flashing on the
screen
> Gas inlet pressure
> Aging or rust on the
electrode
> Recirculation on fluegas
path
> Blokage on flue or wrong
flue
> Electrode position
> Cabeling disconnections
> Combustion calibration
> Electronic board
> Gas valve failiure
1-) Call for authorised service at first
E 80
Problem on electronic gas
valve driver
Boiler does not work, E80
error code flashing on the
screen
> Electronic board
> Gas valve failiure
1-) Call for authorised service at first
E 81
Lock-out for combustion
problem at starting (1)
Boiler does not work, E81
error code flashing on the
screen
> Strong flue blokage
> Combustion problem
> Wrong flue
> Gas inlet pressure
> Aging or rust on the
electrode
> Recirculation on fluegas
path
> Electrode position
> Combustion calibration
1-) Call for authorised service at first
E 82
Lock-out for combustion
problem on Lawa / Lawa Plus
models
Boiler does not work, E82
error code flashing on the
screen
> Recirculation on fluegas
path
> Blokage on flue or wrong
flue
> Combustion calibration
1-) If there is strong wind (ie.wind storm) wait until the wind storm stop
then RESET the boiler
2-) IF problem persist Call for authorised service
E 83
Temporary bad combustion
fault problem on Lawa /
Lawa Plus models
Boiler does not work, E83
error code flashing on the
screen
> Recirculation on fluegas
path
> Blokage on flue or wrong
flue
> Combustion calibration
1-) If there is strong wind (ie.wind storm) wait until the wind storm stop
then RESET the boiler
2-) IF problem persist Call for authorised service