7. Basic settings
The further configuration of the Web-IO is done using a web browser. Enter the IP
address of the Web IO in the browser command line. In the navigation tree, click
Login
and choose
Administrator
as user. By default, no password is assigned and
a click on the login button is sufficient to configure the Web-IO with administrator
rights.
Configuring Inputs and Outputs
In
Basic settings » Inputs/Outputs
you can give individual names to the inputs and
outputs. These names replace the factory default names
Input n
and
Output n
in the
visualization and any message texts. In addition, it must be determined whether the
respective IO channel is to work as input or as output.
Expanded Input settings
For special applications some input properties can be modified:
Input filters
A signal state must be present for the time in milliseconds entered here to be
processed by the Web-IO. For example, bouncing of mechanical contacts can be
suppressed.
Signal inversion
Normally signals greater than 8V are reliably detected as ON. Enabling
Signal
inversion
means voltages greater than 8V are considered OFF.
Expanded output settings
For special applications some output properties can be modified:
Inverted output characteristics
Normally the outputs are switched off in OFF state (i.e. without signal) and switched
on in ON state. By activating the inversion, the output configured in this way acts
exactly reversed.