20
Montage und Verdrahtung
Terminal assignment #57736
Wiesemann &Theis GmbH
Porschestraße 12
42279 Wuppertal
URL: _______________________
#57736
Digital 16xIn/Out
Web-IO 4.0
W&T
www.WuT.de
Power
Status
Warning
Error
Reset
GND
-
Out = ON
In = ON
max. 16mA
+
max. Output Load 16 x 500mA
In/Out Mode Check on Reset
-
- + +
12 - 24 V DC
150mA
+ Output Load
Vcc
+
+ +
+
+
+ +
-
-
-
-
-
-
-
-
+
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
+ +
+
+
+ +
+
-
-
-
-
-
-
-
Klemme 1
1
12
Klemme 2
1
12
Klemme 3
1
12
Klemme 4
1
11
1
4
Vcc
Terminal Vcc
Description / Function
1
GND / Device supply
2
GND / Device supply
3
+ Vcc - Device supply 12-24V max. 2150mA@24V
4
+ Vcc - Device supply 12-24V max. 2150mA@24V
Terminal 1
Bezeichnung / Funktion
1
+ Vdd - Auxiliary voltage 24V 2mA@24V for Input activation
2
Input 0
Switching thr8V
/ Output 0
24V max. 500mA
3
GND / Reference GND for Output
4
GND / Reference GND for Output
5
Input 1
Switching thr8V
/ Output 1
24V max. 500mA
6
+ Vdd - Auxiliary voltage 24V 2mA@24V for Input activation
7
+ Vdd - Auxiliary voltage 24V 2mA@24V for Input activation
8
Input 2
Switching thr8V
/ Output 2
24V max. 500mA
9
GND / Reference GND for Output
10
GND / Reference GND for Output
11
Input 3
Switching thr8V
/ Output 3
24V max. 500mA
12
+ Vdd - Auxiliary voltage 24V 2mA@24V for Input activation
Terminal 2
Description / Function
1
+ Vdd - Auxiliary voltage 24V 2mA@24V for Input activation
2
Input 4 Switching thr8V / Output 4 24V max. 500mA