4.0 SETTING THE OPERATING PANEL & USE
QE SEPCOM SIP BED EASY
no.
Description
Default
value
1
Previous page
-
2
Next page
-
3
Correction time
4 sec
4
Maximum pneumatic pressure when the system runs
4.9 bar
5
Tolerance on the detected absorption of the separator
electric motor in relation to the set point
-1.0 A
6
Minimum pneumatic pressure when the system runs
0.1 bar
7
Pneumatic system pressure in standby mode
1.0 bar
8
Cycle stop delay time in case of alarm
55 sec
no.
Description
Default
value
1
Previous page
-
2
Next page
-
3
Error constant
30
4
Integral reaction time of the pneumatic system in the event of
an error between the measured value and the set value
2 sec
5
Derived reaction time of the pneumatic system in the event of
an error between the measured value and the set value
1 sec
6
The minimum limit of the regulator output beyond which the
analogue output, expressed in points, cannot decrease
0
7
The maximum output limit of the regulator beyond which the
analogue output, expressed in points cannot increase
4096
8
Pneumatic system quick positioning pressure in case of over
current (by-passes PID)
1.0 bar
Screen 3
This page shows the parameters that manage the adjustment of the counter-cone depending on the current
using the PID adjustment. These parameters are very important because incorrect data entry would cause the
system to shut-down.