Householder Information
IMPORTANT!
Your boiler must be commissioned in order to:
-
Validate your warranty
-
Ensure the boiler has been installed correctly and avoid premature failure
-
Set the boiler to its optimum efficiency. Operating conditions for the boiler will vary from site to site, your
commissioning engineer has specialised equipment to check the oil pressure and analyse the exhaust gases for
temperature, smoke and carbon dioxide content.
Your installer will organise the commissioning of your boiler. Should you experience any difficulty locating an
engineer, our service department may be able to provide you with details of an engineer in your area.
“Benchmark” Installation, Commissioning and Service Record Log Book
Please ensure that your installer has completed all sections of the log book (found at the back of this manual).
The log book will be required in the event of any warranty work. Ensure that the service record is completed.
Warranty
Your HRM boiler is under warranty for 2 years from the date of installation.
Warranty Conditions
-
The boiler must be installed and commissioned in accordance with our handbook
-
The boiler must not be repaired, modified or tampered with by any person not authorised by HRM
Extended Warranty
The “Benchmark” and warranty registration document at the end of this manual
should be completed as
appropriate by your installer / engineer. This is your record that the boiler has been correctly installed in accordance
with our recommendations. Return the warranty registration document to HRM in order to qualify for a
further 3 year
warranty of the heat exchanger – a total of 5 years.
Extended Warranty Conditions
-
The boiler must be serviced annually and maintained in accordance with this handbook. The
“Benchmark” service log is located at the back of this manual
-
This warranty is in addition to your statutory and other legal rights
After Sales Service
-
If your boiler fails during the warranty period contact your installer, who will be able to identify the
cause of the problem. If appropriate, your installer will contact us.
-
Under no circumstances should “in warranty” work be undertaken without authorisation from the HRM
service department
-
If you are unable to contact your installer please contact our service department. Quoting your boiler’s
serial number when phoning – this can be found on the cover of this manual.
3
Standard X-ternal & System X-ternal
Handbook
Householder Information
IMPORTANT!
Your boiler must be commissioned in order to:
-
Validate your warranty
-
Ensure the boiler has been installed correctly and avoid premature failure
-
Set the boiler to its optimum efficiency. Operating conditions for the boiler will vary from site to site, your
commissioning engineer has specialised equipment to check the oil pressure and analyse the exhaust gases for
temperature, smoke and carbon dioxide content.
Your installer will organise the commissioning of your boiler. Should you experience any difficulty locating an
engineer, our service department may be able to provide you with details of an engineer in your area.
“Benchmark” Installation, Commissioning and Service Record Log Book
Please ensure that your installer has completed all sections of the log book (found at the back of this manual).
The log book will be required in the event of any warranty work. Ensure that the service record is completed.
Warranty
Your HRM boiler is under warranty for 2 years from the date of installation.
Warranty Conditions
-
The boiler must be installed and commissioned in accordance with our handbook
-
The boiler must not be repaired, modified or tampered with by any person not authorised by HRM
Extended Warranty
The “Benchmark” and warranty registration document at the end of this manual
should be completed as
appropriate by your installer / engineer. This is your record that the boiler has been correctly installed in accordance
with our recommendations. Return the warranty registration document to HRM in order to qualify for a
further 3 year
warranty of the heat exchanger – a total of 5 years.
Extended Warranty Conditions
-
The boiler must be serviced annually and maintained in accordance with this handbook. The
“Benchmark” service log is located at the back of this manual
-
This warranty is in addition to your statutory and other legal rights
After Sales Service
-
If your boiler fails during the warranty period contact your installer, who will be able to identify the
cause of the problem. If appropriate, your installer will contact us.
-
Under no circumstances should “in warranty” work be undertaken without authorisation from the HRM
service department
-
If you are unable to contact your installer please contact our service department. Quoting your boiler’s
serial number when phoning – this can be found on the cover of this manual.
3
Standard X-ternal & System X-ternal
Handbook
7
6
Contents Page
DESCRIPTION
PAGE
Householder Information
Warranty Registration Document
End Of Manual
Warranty
3
Extended
Warranty
3
After
Sales
Service
3
Boiler
Controls:
Wallstar 4
System
Wallstar 5
Wallstar
Combi
6-7
Burner
Lockout
8
Technical Specifications
Boiler
Dimensions:
Wallstar
9
Boiler
Dimensions:
System
Wallstar
10
Boiler
Dimensions:
Wallstar
Combi
11
Technical
Specifications
12
Burner
Settings
13
Boiler Installation
Regulations
14
Boiler
Sizing
14
Refurbishing
An
Old
System
14
System
Protection
14
Boiler
Location
15
Wall
Construction
15
Flue
Terminating
Positions
16
Fuel
Supply
System
17
Oil
Supply
17
Installation Procedure
Wallstar 18-23
System
Wallstar 24-31
Wallstar
Combi
32-40
Condensate
Drain
41
Wiring Diagrams
Wallstar 42
System
Wallstar 42
Wallstar
Combi
43
Boiler Maintenance
Baffle
Removal
44
Fault Diagnosis
Wallstar
Combi
45
Wallstar
Combi
Components
46
Contacts
Tel No: 01953 455400
Fax No: 01953 454483
Email:
or
1
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Contents Page
DESCRIPTION
PAGE
Householder Information
Warranty Registration Document
End Of Manual
Warranty
3
Extended
Warranty
3
After
Sales
Service
3
Boiler
Controls:
Wallstar 4
System
Wallstar 5
Wallstar
Combi
6-7
Burner
Lockout
8
Technical Specifications
Boiler
Dimensions:
Wallstar
9
Boiler
Dimensions:
System
Wallstar
10
Boiler
Dimensions:
Wallstar
Combi
11
Technical
Specifications
12
Burner
Settings
13
Boiler Installation
Regulations
14
Boiler
Sizing
14
Refurbishing
An
Old
System
14
System
Protection
14
Boiler
Location
15
Wall
Construction
15
Flue
Terminating
Positions
16
Fuel
Supply
System
17
Oil
Supply
17
Installation Procedure
Wallstar 18-23
System
Wallstar 24-31
Wallstar
Combi
32-40
Condensate
Drain
41
Wiring Diagrams
Wallstar 42
System
Wallstar 42
Wallstar
Combi
43
Boiler Maintenance
Baffle
Removal
44
Fault Diagnosis
Wallstar
Combi
45
Wallstar
Combi
Components
46
Contacts
Tel No: 01953 455400
Fax No: 01953 454483
Email:
or
1
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Boiler Controls – Wallstar Combi
Control Panel
Mixing Valve
The mixing valve can be adjusted to set the maximum temperature of hot water produced. The valve is graduated
between 1 to 5, the greater the number the hotter the water.
IMPORTANT
-
Too high a setting may cause scalding!
Auxiliary Thermostat
This thermostat maintains the temperature of the boiler for the production of hot water. For best hot water
performance leave the knob set in its maximum position.
Heating Thermostat
The heating thermostat regulates the temperature of the water supplied to the central heating system. To achieve the
heating system performance indicated by the ‘max’ setting, the auxiliary thermostat should also be set to its maximum
position.
Note:
The heating function is interrupted whenever there is a demand for domestic hot water.
Boiler Overheat (Limit) Thermostat
In the unlikely event the boiler overheats, the reset button will trip and cut the power supply to the boiler. Allow the
boiler to cool then press the reset button to reset the thermostat.
IMPORTANT
-
If overheating occurs regularly, consult your installation engineer. There may be a fault with the
central heating system.
Note:
Loss of system pressure may cause the overheat (limit) thermostat to trip; refer to the pressure gauge section
below.
Pressure Gauge
The heating system should be pressurised to approximately 1 bar when cold. Check the pressure occasionally, as
loss of pressure may cause the boiler to overheat.
Please refer to the combi fault diagnosis page for instructions
on pressurising the system.
6
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Boiler Controls – Wallstar Combi
Control Panel
Mixing Valve
The mixing valve can be adjusted to set the maximum temperature of hot water produced. The valve is graduated
between 1 to 5, the greater the number the hotter the water.
IMPORTANT
-
Too high a setting may cause scalding!
Auxiliary Thermostat
This thermostat maintains the temperature of the boiler for the production of hot water. For best hot water
performance leave the knob set in its maximum position.
Heating Thermostat
The heating thermostat regulates the temperature of the water supplied to the central heating system. To achieve the
heating system performance indicated by the ‘max’ setting, the auxiliary thermostat should also be set to its maximum
position.
Note:
The heating function is interrupted whenever there is a demand for domestic hot water.
Boiler Overheat (Limit) Thermostat
In the unlikely event the boiler overheats, the reset button will trip and cut the power supply to the boiler. Allow the
boiler to cool then press the reset button to reset the thermostat.
IMPORTANT
-
If overheating occurs regularly, consult your installation engineer. There may be a fault with the
central heating system.
Note:
Loss of system pressure may cause the overheat (limit) thermostat to trip; refer to the pressure gauge section
below.
Pressure Gauge
The heating system should be pressurised to approximately 1 bar when cold. Check the pressure occasionally, as
loss of pressure may cause the boiler to overheat.
Please refer to the combi fault diagnosis page for instructions
on pressurising the system.
6
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Boiler Controls – Wallstar Combi
Control Panel
Mixing Valve
The mixing valve can be adjusted to set the maximum temperature of hot water produced. The valve is graduated
between 1 to 5, the greater the number the hotter the water.
IMPORTANT
-
Too high a setting may cause scalding!
Auxiliary Thermostat
This thermostat maintains the temperature of the boiler for the production of hot water. For best hot water
performance leave the knob set in its maximum position.
Heating Thermostat
The heating thermostat regulates the temperature of the water supplied to the central heating system. To achieve the
heating system performance indicated by the ‘max’ setting, the auxiliary thermostat should also be set to its maximum
position.
Note:
The heating function is interrupted whenever there is a demand for domestic hot water.
Boiler Overheat (Limit) Thermostat
In the unlikely event the boiler overheats, the reset button will trip and cut the power supply to the boiler. Allow the
boiler to cool then press the reset button to reset the thermostat.
IMPORTANT
-
If overheating occurs regularly, consult your installation engineer. There may be a fault with the
central heating system.
Note:
Loss of system pressure may cause the overheat (limit) thermostat to trip; refer to the pressure gauge section
below.
Pressure Gauge
The heating system should be pressurised to approximately 1 bar when cold. Check the pressure occasionally, as
loss of pressure may cause the boiler to overheat.
Please refer to the combi fault diagnosis page for instructions
on pressurising the system.
6
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Boiler Controls – Wallstar Combi Continued
Time Clock Programming Guide
Setting Up
The outer dial should be set to the current time. Rotate the dial slowly in a clockwise direction, until the correct hour is
approaching the arrow printed on the dial.
Manual Switch Operation
The manual switch will provide On / Timed / Off control, thereby allowing manual control of the heating without
disrupting the timed (tappet) settings.
Programming Switching Times
One tappet is equal to 15 minutes. Set the number of tappets to the outer edge of the dial, equal to the duration of
time the heating is required to be switched on.
Power Neon Lamp
The lamp is illuminated when the mains supply to the boiler is switched on.
Limit Neon Lamp
The lamp is illuminated when there is power to the controls, but the boiler has overheated. When the limit reset is
pressed this lamp should extinguish.
Lockout Neon Lamp
The lamp is illuminated when there is power to the controls, but the burner has not fired correctly.
Arrow
Manual Switch Position
I
=
On (top position)
=
Timed (centre position)
0
=
Off (bottom position)
Tappets Position
In = Off
Out = On
7
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
Boiler Controls – Wallstar Combi
Control Panel
Mixing Valve
The mixing valve can be adjusted to set the maximum temperature of hot water produced. The valve is graduated
between 1 to 5, the greater the number the hotter the water.
IMPORTANT
-
Too high a setting may cause scalding!
Auxiliary Thermostat
This thermostat maintains the temperature of the boiler for the production of hot water. For best hot water
performance leave the knob set in its maximum position.
Heating Thermostat
The heating thermostat regulates the temperature of the water supplied to the central heating system. To achieve the
heating system performance indicated by the ‘max’ setting, the auxiliary thermostat should also be set to its maximum
position.
Note:
The heating function is interrupted whenever there is a demand for domestic hot water.
Boiler Overheat (Limit) Thermostat
In the unlikely event the boiler overheats, the reset button will trip and cut the power supply to the boiler. Allow the
boiler to cool then press the reset button to reset the thermostat.
IMPORTANT
-
If overheating occurs regularly, consult your installation engineer. There may be a fault with the
central heating system.
Note:
Loss of system pressure may cause the overheat (limit) thermostat to trip; refer to the pressure gauge section
below.
Pressure Gauge
The heating system should be pressurised to approximately 1 bar when cold. Check the pressure occasionally, as
loss of pressure may cause the boiler to overheat.
Please refer to the combi fault diagnosis page for instructions
on pressurising the system.
6
Standard Wallstar, System Wallstar &
Wallstar Combi Manual
This thermostat maintains the temperature of the boiler for the production of hot water. Pre-set at maximum position.