INSTALLATION AND COMMISSIONING CHECKLIST: SETTING GATE LIMITS
Installation and Commissioning Checklist: Setting Gate Limits
Complete Step
Description
5.3.2-F. Once you’ve reached the master password
use the STOP button to lock the parameter
in. To do this you must HOLD the stop
button down until a check mark appears
by the master password.
Once the parameter value for the master
password is locked in, press the STOP
button again to return the underscore to
the parameter 999 on the left.
5.3.3
STEP THREE: PROGRAMMING THE
SPEEDGATE
5.3.3-A. Pull manual brake disconnect cable
located inside each column and lock the
cable clamp into the groove provided.
5.3.3-B. Move gate panels to halfway point
between open and closed positions.
PANELS HALF-OPEN: TOP VIEW
5.3.3-C. Release manual brake disconnect (pull
down on the cable and remove it from the
groove) in each column to allow gate to be
moved under power.
5.3.3-D. Clear the gate travel area of all
obstructions/persons, and place
appropriate warning/signaling devices
to allow for automatic gate movement.
Summary of Contents for SPEEDGATE
Page 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 SPEEDGATE INSTALLATION...
Page 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 SPEEDGATE INSTALLATION...
Page 59: ...PDXT PDXT C and PDTT Electrical Point to Point Diagrams 1...
Page 60: ......
Page 61: ...PDXT PDXT C and PDTT Electrical Point to Point Diagrams 2...
Page 62: ......
Page 63: ...PDXT PDXT C and PDTT Electrical Point to Point Diagrams 3...
Page 64: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 141: ......