Gas Conversion and Specifications
e. On completion of the main burner adjustments, check all gas connections for leakages and then
turn ‘OFF’ the main burners at the gas control knob. Turn off the main gas supply.
Gas Type Identification Label
On completion of the gas conversion, replace the gas type identification label located at:-
- The rear of the appliance, above the gas connection.
- Beside the rating plate.
Commissioning
Before leaving the converted installation;
1.
Check all gas connections for leakages using soapy water or other gas detecting equipment.
2.
Check the following functions in accordance with the operating instructions specified in the
'Operation' section of this manual.
•
Light the Main Burners.
•
Check the Thermostat operation.
•
Ensure that all the controls operate correctly.
NOTE: If for some reason it is not possible to get the unit to operate correctly, shut off the gas
supply and contact the supplier of this unit.
Gas Specifications
NOTE:
(*)
The burner operating pressure is to be measured at the upper test point (Supply
Pressure) on the gas control valve located behind the access door and through
the access hole in the control panel, this is to be carried out with both burners
operating at the 'High Flame' setting.
Natural Gas
LPG
Main Burner Injectors
4.30 mm
2.40 mm
Aeration Plate
20 x Ø 9.55 holes
16 x Ø 9.55 holes
Operating Pressure
0.95 kPa (*)
(3.6” w.c.)
2.6 kPa (*)
(10.5” w.c.)
Supply Pressure
1.13 - 3.40 kPa
(4.5” - 13.5” w.c.)
2.75 - 3.40 kPa
(11” - 13.5” w.c.)
WARNING:
D
O
NOT
USE
A
NAKED
FLAME
TO
CHECK
FOR
GAS
LEAKAGES
.