Digital Outputs 750-506
:$*2
Ç
,
2
Ç
6<67(0
2
Technical Data:
Item Number 750-
506
Number of outputs
2
Current consumption (internal)
15 mA
Nominal voltage
24V DC (-15%/+20%)
Kind of load
resistive, inductive, lamps
Output current (DC)
0.5 A
Diagnostics
open circuit, overload
Current consumption (internal)
15 mA typ. + load
Isolation
500 V system / power supply
Internal bit width
4 in, 4 out
Configuration
without address or configuration adjustment
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP; 0.08 to 2.5mm
2
Dimensions (mm)WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
The output bits control the state of the outputs.
Bit 3
Bit 2
Bit 1
Bit 0
function
no function
no function
controls O2
controls O1
The input bits show the state of the outputs.
Bit 3
Bit 2
Bit 1
Bit 0
function
diagnostics O2
diagnostics O2
diagnostics
O1
diagnostics O1
output follows
output bit
0
0
0
0
no load is
connected
0
1
0
1
short circuit
1
0
1
0
power supply
too low*
1
1
1
1
*The diagnostic bits refer to a hysteresis: If the voltage of the field side is higher than
11V in the falling circle, they are switched on. If the voltage is lower than 15,5 V in the