Analog Inputs 750-456
:$*2
Ç
,
2
Ç
6<67(0
4
The numerical format for Siemens
In addition to the full 16 bit indication of the measured value it is possible to use the
Siemens format. The measured value is represented by the most significant 12 Bits. The
3 least significant bits are reserved for diagnostic and status purposes. (750-456/000-
001).
Input voltage
±10V
Binary value
X : without
meaning
F : short circuit
or
F : open circuit
Ü : overflow
X F Ü
Hex.
Dec.
>10
0111 1111 1111 1
0 0 1
7F F9
32761
10
0111 1111 1111 1
0 0 0
7F F8
32760
5
0110 0000 0000 0
0 0 0
60 00
24576
2,5
0101 0000 0000 0
0 0 0
50 00
20480
1,25
0100 1000 0000 0
0 0 0
48 00
18432
0,0049
0100 0000 0000 1
0 0 0
40 08
16392
0
0100 0000 0000 0
0 0 0
40 00
16384
-2,5
0011 0000 0000 1
0 0 0
30 08
12296
-5
0010 0000 0000 0
0 0 0
20 00
8192
-7,5
0001 0000 0000 0
0 0 0
10 00
4096
-10
0000 0000 0000 1
0 0 0
00 00
8
<-10
0000 0000 0000 0
0 0 1
00 01
1
If you hve questions about the formatting of this data, please contact WAGO for
the I/O System technical support.