Application in Explosive Environments
•
11
Installation regulations
WAGO-I/O-SYSTEM 750
Modular I/O-System
Danger
For the use of WAGO-I/O SYSTEM 750 (electrical operating means) with Ex
approval the observance of the following points is mandatory:
•
The electrical operating means are exclusively suitable for applications in
explosion endangered areas (Europe Group II, Zone 2 or America: Class I,
Division 2, Group A, B, C, D) or in non explosion endangered areas!
•
Ensure that only approved modules of the electrical operating means will
be used. Replacement of components can jeopardize the suitability of the
system in explosion endangered zones!
•
Only disconnect and/or connect electrical operating means when the
voltage supply is isolated or when a non-explosive atmosphere has been
ascertained!
•
Adhere to the specified data regarding voltage supply and fusing. (See
data on the fuse holder)!
i
Further Information
Proof of certification is available on request.
Also take note of the information given on the module technical information
sheet.