Data exchange module 750-654
:$*2
Ç
,
2
Ç
6<67(0
5
Structure of the in- and output data for Profibus (from firmware WH)
The ID 179 (hex: 0xB3), (
Data consistence over 4 Byte) is used.
Outputs
Byte
Description
D0
Output byte0
D1
Output byte1
D2
Output byte2
D3
Output byte3
Inputs
Byte
Description
D0
Input byte0
D1
Input byte1
D2
Input byte2
D3
Input byte3
For the ID 188 (hex.: 0xBC), Data consistence over 6 Byte is used, input and output data
are now as follows:
Outputs
Byte
Description
D0
Control byte
D1
Output byte0
D2
Output byte1
D3
Output byte4
D4
Output byte2
D5
Output byte3
Inputs
Byte
Description
D0
Statusbyte
D1
Input byte0
D2
Input byte1
D3
Input byte4
D4
Input byte2
D5
Input byte3
For a S7 PLC the function code SFC14 and SFC15 must be used because the data length
is more than 4.
Attention:
The control byte allows the changing of the registers of the module. It must always be 0
in order to avoid a change in the registers. A wrong mapping can change the function of
the module!