86 • Programmable Field Bus Controller 750-833
Parameterization of the Controllers
WAGO-I/O-SYSTEM
750
Bus System
Description
Value
Meaning
Start-up via DPV1 channel
The cyclic data exchange
locked
*)
occurs after a successful parameterization and
configuration
released
occurs after a release on the acyclic C1 channel
or C2 channel
Slot allocation
Assigning the slots for acyclic read and write is
performed
DPV1
compatible
*)
according DPV1 format
S7 compatible
according S7 format
*)
Default settings
The complete data block encompasses 26 parameterized bytes. The first 10
bytes are laid down via the DP and DPV1 standard. The others receive
manufacturer specific parameters.
Byte No.
Bit No.
Value
Meaning
Standard Parameters
0
0-7
Station status (see EN 50170)
1
0-7
2-255
Watchdog factor 1
2
0-7
2-255
Watchdog factor 2
Watchdog:
The response monitoring is the result of
Watchdog_Factor_1 x Watchdog_Factor_2 x 10 ms (1 ms)
3 0-7
11-255
Min
T
SDR
,
Earliest time in T
Bit
after which the slave can reply
4
0-7
183, 0xB7
Manufacturer identification (high byte)
5
0-7
86, 0x56
Manufacturer identification (low byte)
6
0-7
Group membership,
Broad and multicast telegrams (SYNC, FREEZE)
7
0-7
DPV1 status 1 (see EN 50170)
8
0-7
DPV1 status 2 (see EN 50170)
9
0-7
DPV1 status 3 (see EN 50170)
Manufacturer Parameters
10
0-7
0
Table 0, register 0 LB, reserved
11
0-7
0
Table 0, register 0 HB, reserved
12
0-7
0
Table 0, register 1 LB, reserved
13
0-7
0
Table 0, register 1 HB, reserved
Table 0, register 2 LB
0
Device diagnostics locked
0
1
*)
Device diagnostics released
0
Internal bus restart after fault: POWER-ON-RESET
1
1
*)
Internal bus restart after fault: AUTORESET
14
2-7 0
reserved
15
0-7
0
Table 0, register 2 HB, reserved
Table 0, register 3 LB
0-2 '011' reserved
0
Data format byte orientated I/O modules: INTEL
3
1
*)
Data format byte orientated I/O modules: MOTOROLA
16
4-7 '1100' reserved