180 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM
750
Bus System
5.4.1.13 16 DO I/O Module
Module
Identification
hex
Identification
dec
750-5dd 16 DO, Buerkert 8644 monost. 16 DO
0x21
33
Process Image
Input Image
in [Bit]
Output Image
in [Bit]
Internal bus
0
16
PROFIBUS DP
0
16
PFC (CPU)
0
16
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied to the I/O module
not plug fitted
- ignored by the coupler
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0 0 0 1 0
1
7 6 5 4 3 2 1 0
0 0 0 1 0 0 1 0
2
7 6 5 4 3 2 1 0
SV7
SV6
SV5
SV4
SV3 SV2 SV1 SV0
2
7 6 5 4 3 2 1 0
SV15
SV14
SV13
SV12
SV11 SV10 SV9 SV8
PFC
6
0
1
Module is mapped into the field bus PA and PFC-PA
Module is exclusively mapped into the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SV0
0
Substitute channel 1
SV1
1
Substitute channel 2
SV2
2
Substitute channel 3
SV3
3
Substitute channel 4
SV4
4
Substitute channel 5
SV5
5
Substitute channel 6
SV6
6
Substitute channel 7
SV7
7
Substitute channel 8
SV8
0
Substitute channel 9
SV9
1
Substitute channel 10
SV10
2
Substitute channel 11
SV11
3
Substitute channel 12
SV12
4
Substitute channel 13
SV13
5
Substitute channel 14
SV14
6
Substitute channel 15
SV15
7
Substitute channel 16
Italic
cannot be changed