I/O Modules
•
205
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0 0
Diag
En0
0 0
1
7 6 5 4 3 2 1 0
1
1
ID5 ID4 ID3 ID2 ID1 ID0
2
7 6 5 4 3 2 1 0
0
0 0 0 0 0 0 0
3
7
6
5
4
3
2
1
0
0
0
0
0
1
1
1
0
Block length in Byte
4
15
14
13
12
11
10
9
8
0
0
0
0
0
1
0
1
Block module
PROFIsafe
5
7
6
5
4
3
2
1
0
F_Slot
PROFIsafe
module slot
6
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
Specifier
7
7
6
5
4
3
2
1
0
0
0
F_CRC_Len
F_SIL
F_Chk
_iPar
F_Chk
SeqNo
F_Prm_Flag1
8
7
6
5
4
3
2
1
0
F_Par_Ver
F_Block_ID
0
0
0
F_Prm_Flag2
9
15
14
13
12
11
10
9
8
F_Src_Addr_High
10
7
6
5
4
3
2
1
0
F_Src_Addr_Low
F_Source_Address (1...65534)
11
7
6
5
4
3
2
1
0
F_Dst_Addr_High
12
7
6
5
4
3
2
1
0
F_Dst_Addr_Low
F_Destination_Address (1...65534)
13
15
14
13
12
11
10
9
8
F_WD_Time_High
14
7
6
5
4
3
2
1
0
F_WD_Time_Low
F_Watchdog_Time in ms (1…65535)
15
7
6
5
4
3
2
1
0
F_CRC_High
16
7
6
5
4
3
2
1
0
F_CRC_Low
F_Parameter_CRC (CRC1)
PFC
6
0
1
Module is mapped in the field bus and PFC-PA
Module is exclusively mapped in the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics locked (default)
Diagnostics released
ID5 .. ID0
Order number less 630 (e. g. 750-650 would be coded as (650-630) = 20)
F_Slot 2..63
PROFIsafe
module slot
F_ChkSeqNo 0
1
The consecutive number is not considered in the CRC2 calculation
The consecutive number is considered in the CRC2 calculation
F_Chk_iPar
0 no i-Parameter
F_SIL 0..3
0
1
2
3
SIL class
SIL1
SIL2
SIL3
none
F_CRC_Len
1 2 Byte CRC because of a user data length of less than 12 Byte
F_Block_ID
0 F-Host/F-Slave-Communication-Connection
F_Par_Ver
7..6
0 Valid for
PROFIsafe
-Profil versions 1.00 – 1.99
F_Src_Addr 1..65534
PROFIsafe
-Address of the F-Host
F_Dst_Addr 1..65534
PROFIsafe
-Address of the F-Slave
F_WD_Time 150..10000
PROFIsafe
-Watchdogtime in ms
F_CRC any
PROFIsafe
-CRC
Italic
Cannot be changed