Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.7
2 (1) DO I/O Modules with 1 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-507, 750-522, 750-523 (1 DO),
750-5dd 2 DO/2 DIA-DI/2 DIA,
Diagnostics in the input process image
0x30 48
750-507, 750-522, 750-523 (1 DO),
750-5dd 2 DO/2 DIA
0x20 32
*750-507, *750-522, 750-523 (1 DO),
*750-5dd 2 DO/2 DIA
0x00 0
Process Image
Input Image
in [Bit]
Output Image
in [Bit]
Internal bus
2
2
Diagnostics in the input process image
Yes
2 (1)
2 (1)
PROFIBUS DP
No 0
2
(1)
PFC (CPU)
2
1)
(0
2)
) 2
(1)
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied to the I/O module
not plug fitted
- ignored by the coupler
Diagnostics is mapped into the
Input-PAB
The diagnostics information of the I/O module
is
(only for *-Modules)
released
- mapped into the input process image
locked
*)
- not mapped into the input process image
Diagnostics channel x
The diagnostics information of the correspond-
ing channel is
released
- transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter (up to Firmware 06)
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0
Diag
En1
Diag
En0
0 0
1
7 6 5 4 3 2 1 0
0 0 0 0 0 0 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0
SV1 SV0
Parameter (from Firmware 07)
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug PA-
Diag
0 0 0 0
1
7 6 5 4 3 2 1 0
0 0 0 1 0 0 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0
SV1 Diag
En1
SV0 Diag
En0