188 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM
750
Bus System
5.4.2.3
2 AO I/O Modules
Module
Register Communication
possible
Identification
hex
Identification
dec
Yes 0xF2
242
750-550, 750-552, 750-554,
750-556, 750-560, 750-585,
750-5aa 2 AO
Nein 0x61
97
Process Image
Input Image
in [Byte]
Output Image
in [Byte]
Internal bus
6
6
Register communication possible
Yes 6
6
PROFIBUS DP
No 0
4
PFC (CPU)
0
4
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied to the I/O module
not plug fitted
- ignored by the coupler
Diagnostics channel x
The diagnostics information of the correspond-
ing channel is
released
- transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute channel x
0x0000 or 0x8000
0 or -32767
...
0x7FFF
...
32767
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0
Diag
En1
Diag
En0
0 0
1
7 6 5 4 3 2 1 0
1 0
ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 9 8 7
SubVal_Ch1_HB
3
7 6 5 4 3 2 1 0
SubVal_Ch1_LB
4
15 14 13 12 11 10 9 8
SubVal_Ch2_HB
5
7 6 5 4 3 2 1 0
SubVal_Ch2_LB