2.5.9 Wire connection
All components have CAGE CLAMP® connections.
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded
and fine–stranded conductors. Each clamping unit accommodates one con-
ductor.
Fig. 2-9: CAGE CLAMP® Connection
g0xxx08x
The operating tool is inserted into the opening above the connection. This
opens the CAGE CLAMP
®
. Subsequently the conductor can be inserted into
the opening. After removing the operating tool, the conductor is safely
clamped.
More than one conductor per connection is not permissible. If several con-
ductors have to be laid at a connection, then they should be laid in off-course
wiring; e.g. together with WAGO transfer terminals.
Attention
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be
used.
Ferrule:
Length
8 mm
Nominal cross section
max.
1 mm
2
for 2 conductors with 0.5 mm
2
each
WAGO Product
216-103
or products with comparable properties