The WAGO-I/O-SYSTEM 750
•
27
Power Supply
WAGO-I/O-SYSTEM 750
DeviceNet
Attention
Some bus modules have no or very few power contacts (depends on the I/O
function). Due to this, the passing on of the relevant potential is disrupted. If
a field supply is required for subsequent bus modules, then a power supply
module must be used.
Note the data sheets of the bus modules.
In the case of a node setup with different potentials, e.g. the alteration from
DC 24 V to AC 230V, a spacer module should be used. The optical separa-
tion of the potentials acts as a warning to heed caution in the case of wiring
and maintenance works. Thus, the results of wiring errors can be prevented.
2.6.3.2 Fusing
Internal fusing of the field supply is possible for various field voltages via an
appropriate power supply module.
750-601
24 V DC, Supply / Fuse
750-609
230 V AC, Supply / Fuse
750-615
120 V AC, Supply / Fuse
750-610
24 V DC, Supply / Fuse / Diagnosis
750-611
230 V AC, Supply / Fuse / Diagnosis
Fig. 2-14: Supply module with fuse carrier (Example 750-610)
g0xxx09x