Fieldbus Coupler/Controller • 45
Fieldbus Coupler 750-306
WAGO-I/O-SYSTEM 750
DeviceNet
3.1.2.7 Setting the Baud Rate
The fieldbus coupler supports 3 different Baud rates, 125 kBaud, 250 kBaud
and 500 kBaud. DIP switches 7 and 8 are used to set the baud rate.
Baud rate
DIP7
DIP8
125 kBaud
*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
12
34
5
ON
67
8
1
2
3
4
5
6
7
8
ON
g012541x
Fig. 3-7: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) on a
station (node) with the address MAC
ID 1.
*)
Presetting
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the
buscoupler. Turn off and on the power supply for the fieldbus Coupler to ac-
cept the DIP switch change.
The default setting is Baud rate 125 kB.
3.1.3 Operating System
Following is the configuration of the master activation and the electrical in-
stallation of the fieldbus station.
After switching on the supply voltage, the Coupler performs a self-test of all
functions of its devices, the I/O module and the fieldbus interface. Following
this, the I/O modules and the present configuration is determined, whereby an
external, not visible list is generated.
In the event of a fault, the Coupler changes to the "Stop" condition. The "I/O"
LED flashes red. After clearing the fault and cycling power, the Coupler
changes to the "Fieldbus start" status and the "I/O" LED lights up green.
Fig. 3-8: Operating system 750-306
g012113d