765-4102/0100-0000
Commissioning
Product manual | Version: 2.1.0
67
8PORT IOL-B FLD PN DC 24V 2.0A
3. Configure the ports
4. Set the parameters
ð
The parameters are imported from the GSDML file.
10.2.1.1.1 Selecting the Product
Select the product used from the device catalog.
Product: 765-4102
Name: 8PORT IOL-B FLD PN DC 24V 2.0A
10.2.1.1.2 Configuring the PROFINET Station Name and IP Address
When delivered and after a factory rest, the IO device has no PROFINET product name,
and the IP address is 0.0.0.0.
The IO-Device requires a unique PROFINET product name so the IO controller can com-
municate with the IO device.
Use the engineering software to assign the IO device a PROFINET product name.
The IO controller configures the IP address when PROFINET starts up.
10.2.1.1.3 Parameterizing Ports
Parameterize the ports using the information in section
8
10.2.1.1.4 Parameterizing the Submodule
Parameterize the submodule using the information in section
8
10.2.2 WAGO Webserver I/O Field
10.2.2.1 Opening WAGO Webserver I/O Field
This section describes how you can use the integrated software “WAGO Webserver I/O
Field” to get access to detailed information on the current operating state of the product
and make settings to affect the product’s behavior.
ü
Requirement: Opening the user interface of WAGO Webserver I/O Field requires that
product’s IP address is configured and known.
•
Proceed as follows:
Enter the following text in the address bar of your Web browser to address the prod-
uct:
http://<IP-address-according-to-configuration>
e.g.,
http://192.168.10.2
.
ð
The
Dashboard
of WAGO Webserver I/O Field appears. You can now use the func-
tions described below.