765-4102/0100-0000
Commissioning
Product manual | Version: 2.1.0
127
8PORT IOL-B FLD PN DC 24V 2.0A
The following table lists port-specific diagnostic information.
Table 72: Port-Specific Diagnostics
Node Name
Node Class
Access
Description
DiagnosticsPin1, Diagnos-
ticsPin2, DiagnosticsPin4
Variable
Read
Diagnostics on pin 1, pin 2
or pin 4; the numerical
value contains bit-coded
information:
Bit 0: short circuit
Bit 1: overload protection
Bit 2: overtemperature pro-
tection
Bit 3: overvoltage protec-
tion
Bit 4: overcurrent
Bit 5: undercurrent
Bit 6: overtemperature
Bit 7: undertemperature
Bit 8: overvoltage
Bit 9: undervoltage
Bit 10: watchdog
0: diagnostics inactive
1: diagnostics active
10.2.5.1.6 Reading out Statistics
The OPC UA server provides nodes with statistical information. For example, the OPC
UA client can read out the maximum measured current on pin 1 of a port in the
MaxCur-
rentPin1
node. The path to this node is:
Root > Object > DeviceSet > [device-name] > IOLinkMaster > PortXX
> Statistics > Current / Temperature / Voltage
The following table lists port-specific statistical information:
Table 73: Port Specific Statistical Information
Node Name
Node Class
Access
Description
MaxCurrentPin1,
MaxCurrentPin2,
MaxCurrentPin4
Variable
Read
Maximum current on pin 1,
pin 2 or pin 4 since the
value was reset; unit: mA
MinCurrentPin1,
MinCurrentPin2,
MinCurrentPin4
Variable
Read
Minimum current on pin 1,
pin 2 or pin 4 since the
value was reset; unit: mA
MaxTemperaturePin1,
MaxTemperaturePin2,
MaxTemperaturePin4
Variable
Read
Maximum temperature on
pin 1, pin 2 or pin 4 since
the value was reset; unit:
°C
MinTemperaturePin1,
MinTemperaturePin2,
MinTemperaturePin4
Variable
Read
Minimum temperature on
pin 1, pin 2 or pin 4 since
the value was reset; unit:
°C
MaxVoltagePin1,
MaxVoltagePin2,
MaxVoltagePin4
Variable
Read
Maximum voltage on pin 1,
pin 2 or pin 4 since the
value was reset; unit: mV