765-4102/0100-0000
Planning
44
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 33: Parameters of the “IO-Link XX I / XX O + PQI” Submodule
Parameter Group
Parameters
Default
Value Range
Description
IO-Link port parame-
ters
Enable port diagnos-
tics
1
0: disable
The PROFINET port
diagnostics are dis-
abled, i.e. no diag-
nostic alarms are
triggered
1: enable
PROFINET port di-
agnostics are en-
abled.
Enable process
alarm (device notifi-
cation)
1
0: disable
PROFINET process
alarms are disabled
1: enable
PROFINET process
alarms are enabled
Configuration source 1
0: PDCT (Port and
Device Configuration
Tool)
Configuration is per-
formed via a “port
and product configu-
ration tool”
1: PNIO
Configuration is per-
formed via the
PROFINET IO-Con-
troller
IO-Link port parame-
ters (continued)
Enable input fraction 1
0: disable
Input fraction is
switched off
1: enable
Input fraction is
switched on
Enable pull/plug
1
0: disable
PROFINET pull/plug
alarms are disabled
1: enable
PROFINET pull/plug
alarms are enabled
Port mode
2
0: deactivated
Port operating mode:
Pin 4 is disabled
1: IOL_Manual
Pin 4 is operated as
an IO-Link port with
manual configuration
(GSD-based port
configuration)
2: IOL_Autostart
Pin 4 is operated as
an IO-Link port with
automatic configura-
tion (plug and play).
3: DI_C/Q
Pin 4 is a digital input
4: DO_C/Q
Pin 4 is a digital out-
put