765-4102/0100-0000
Diagnostics
134
Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 86: Process Alarms for IO-Link Device Diagnostics
Channel Error
(PROFINET)
Extended
Channel Error
Type
(PROFINET)
Description of the Error Function
on the Connected IO-Link Device
Corrective Action on the Con-
nected
IO-Link Device
0x9500
0x4210
Device overheating
Eliminate heat source
0x9500
0x4220
Device undercooling
Insulate IO-Link device
0x9500
0x5000
Hardware error in device
Replace IO-Link device
0x9500
0x5010
Malfunction of a component
Repair for replacement
0x9500
0x5011
Loss of data of non-volatile memory
Check batteries
0x9500
0x5012
Batteries too weak
Replace batteries
0x9500
0x5100
General error in the power supply
Check availability
0x9500
0x5101
Fuse blown/open
Replace fuse
0x9500
0x5110
Overvoltage in primary power supply
Check tolerance
0x9500
0x5111
Undervoltage in primary power supply Check tolerance
0x9500
0x5112
Error in additional power supply
Check tolerance
0x9500
0x6000
Error in device software
Check firmware version
0x9500
0x6320
Parameter error
Check datasheet and values
0x9500
0x6321
Missing parameter(s)
Check datasheet
0x9500
0x6350
Parameter change
Check configuration
0x9500
0x7700
Wire break on a lower-level device
Check installation
0x9500
0x7701 –
0x770F
Wire break of lower-level device
1...15
Check installation
0x9500
0x7710
Short circuit
Check installation (device)
0x9500
0x7711
Grounding fault
Check installation
0x9501
0x0C00
Technology-specific application error
Reset device
0x9501
0x0C01
Simulation active
Check operating mode
0x9501
0x0C10
Value range of a process variable ex-
ceeded
Process data insecure
0x9501
0x0C20
Measurement overrange
Check application
0x9501
0x0C30
Process variable value below value
range
Process data insecure
0x9501
0x0C40
Maintenance required
Cleaning
0x9501
0x0C41
Maintenance required
Refill
0x9501
0x0C42
Maintenance required
Replacement of wear parts