Process Image 41
753-1630 SMI Master Module 230 V AC
Manual
Version 1.2.0 FW/HW Version 02/01
Pos: 79 /Serie 753 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/FT&K/Prozessabbild 753-1630, -1631/Prozessabbild 753-1630, -1631 - Erweitertes Control-/Statusbyte @ 28\mod_1478705544660_21.docx @ 386890 @ 2 @ 1
5.2
Extended Control/Status Byte
The SMI master module also has an extended control/status byte.
Table 18: Control byte C1
Control byte C1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
-
-
-
-
Controller
locking
Energy
saving mode
Controller
failure
monitoring
-
Not used
Controller
failure
monitoring
Heartbeat of the PLC for controller failure monitoring
Energy saving
mode
Energy saving mode:
0 – Deactivate energy saving function
1 – Activate energy saving function
Controller
locking
Controller locking:
0 – Deactivate
1 – Activate
Table 19: Status Byte S1
Status Byte S1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
DI
-
-
-
-
Controller
locking
Energy
saving mode
Forced
position
-
Not used
Forced position Forced position:
0 – Inactive
1 – Active
Energy saving
mode
Energy saving mode:
0 – Inactive
1 – Active
Controller
locking
Controller locking:
0 – Inactive
1 – Active
DI
Status of the digital input:
0 – Low
1 – High