I/O Modules • 155
Process Data Architecture for MODBUS/TCP
WAGO-I/O-SYSTEM 750
Linux Fieldbus Coupler
The above Counter Modules have a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. The
following tables illustrate the Input and Output Process Image, which has a
total of 4 words mapped into each image. Word alignment is applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
S0
Status byte of Counter 1
1
D1
D0
Counter Value of Counter 1
2
-
S1
Status byte of Counter 2
3
D3
D2
Counter Value of Counter 2
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
C0
Control byte of Counter 1
1
D1
D0
Counter Setting Value of Counter 1
2
-
C1
Control byte of Counter 2
3
D3
D2
Counter Setting Value of Counter 2
Pulse Width Modules
750-511, (and all variations)
The above Pulse Width modules have a total of 6 bytes of user data in both
the Input and Output Process Image (4 bytes of channel data and 2 bytes
of control/status). The two channel values are supplied as 16 bits. Each
channel has its own control/status byte. The following table illustrates the
Input and Output Process Image, which has a total of 4 words mapped into
each image. Word alignment is applied.