I/O Modules • 161
Process Data Architecture for MODBUS/TCP
WAGO-I/O-SYSTEM 750
Linux Fieldbus Coupler
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 D0 S DALI
Response
Status
byte
1
D2
D1
Message 3
DALI Address
3
D4
D3
Message 1
Message 2
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 D0 C
DALI command,
DSI dimming value
Control byte
1 D2 D1 Parameter
2
DALI
Address
3 D4 D3 Command-
Extension
Parameter 1
EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the
Input and Output Process Image (3 bytes of module data and 1 byte of
control/status). The following tables illustrate the Input and Output Process
Image, which have 2 words mapped into each image. Word alignment is
applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 D0 S Data
byte
Status
byte
1 D2 D1
Data
bytes
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
C
not used
Control byte
1 - -
not
used