52
•
Linux Fieldbus Coupler 750-860
Error Indication (IO LED)
WAGO-I/O-SYSTEM
750
Linux Fieldbus Coupler
The blink code is repeated cyclically until the error is corrected and/or the
Linux fieldbus coupler is rebooted.
The following table lists the types of errors with the associated blink codes:
Error ar-
gument
Error description
Remedy
Fault Code 1: Hardware and Configuration Fault
1
Overflow of the internal buffer
memory for the inline code.
Turn off the supply voltage of the Linux
fieldbus coupler, reduce the number of
modules and turn on the supply voltage again.
If the error remains, replace the coupler
4
Error when writing to
EEPROM
Switch off the supply voltage of the Linux
fieldbus coupler, replace the coupler and
switch on again.
5
Fault when reading the serial
EEPROM
Switch off the supply voltage of the Linux
fieldbus coupler, replace the coupler and
switch on again.
6
The I/O module configuration
after an internal bus reset
differs from the one after the
last I/O-IPC start-up.
Restart the Linux fieldbus coupler by turning
the power supply off and on again.
14
Maximum number of gateway
modules or mailbox modules
exceeded
Reduce the number of corresponding
modules to a valid number.
Error code 4: Physical error of the internal bus
n*
Interruption of the internal bus
behind the nth I/O module with
process data.
Turn off the supply voltage of the Linux
fieldbus coupler, replace the (n+1)th I/O
module with process data and turn on the
supply voltage again.
Error code 6: Node configuration error
8
Error during process image
generation
Reduce the number of I/O modules on the
node