Fieldbus
Communication
•
235
MODBUS
Functions
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Register address 0x1005 (MODBUS Address 404102)
Designation
Stop Watchdog, WD_AC_STOP_MASK
Access
read / write
Default 0x0000
Description
This register is used to stop the watchdog timer by entering a value of
0xAAAA followed by 0x5555.
Register address 0x1006 (MODBUS Address 404103)
Designation
While watchdog is running, WD_RUNNING
Access read
Default 0x0000
Description
Current watchdog status.
at 0x0000: Watchdog not active,
at 0x0001: Watchdog active.
at 0x0002: Watchdog exhausted.
Register address 0x1007 (MODBUS Address 404104)
Designation
Restart watchdog, WD_RESTART
Access
read / write
Default 0x0001
Description
This register restarts the watchdog timer by writing a value of 0x1 into it.
If the watchdog was stopped before the overrun, it is not restarted.
Register address 0x1008 (MODBUS Address 404105)
Designation
Simply stop watchdog WD_AC_STOP_SIMPLE
Access
read / write
Default 0x0000
Description
This register stops the watchdog by writing the value 0x0AA55 or 0X55AA
into it. The watchdog timeout fault is deactivated and it is possible to write
in the watchdog register again. If there is an existing watchdog fault, it is
reset
Register address 0x1009 (MODBUS Address 404106)
Designation
Close MODBUS socket after watchdog timeout
Access
read / write
Description
0: MODBUS socket is not closed
1: MODBUS socket is closed