206
•
Fieldbus Communication
BACnet/IP
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
Tab. 4-38: IAs/BIBBs of the six standardized device profiles
B-OWS
B-BC
B-AAC
B-ASC
B-SA
B-SS
IA
Data Sharing
DS-RP-A,B DS-RP-A,B DS-RP-B DS-RP-B DS-RP-B
DS-RP-B
DS-RPM-A DS-RPM-A,B DS-RPM-B DS-WP-B DS-WP-B
DS-WP-A DS-WP-A,B DS-WP-B
DS-WPM-A DS-WPM-B DS-WPM-B
DS-COVU-A,B
Alarm &
AE-N-A AE-N-I-B AE-N-I-B
Event Mgmt
AE-ACK-A AE-ACK-B AE-ACK-B
AE-INFO-A AE-INFO-B AE-INFO-B
AE-ESUM-A AE-ESUM-B
Scheduling
SCHED-A SCHED-E-B SCHED-I-B
Trending
T-VMT-A T-VMT-I-B
T-ATR-A T-ATR-B
Device &
DM-DDB-A,B DM-DDB-A,B DM-DDB-B DM-DDB-B
Network
DM-DOB-A,B DM-DOB-A,B DM-DOB-B DM-DOB-B
Mgmt
DM-DCC-A DM-DCC-B DM-DCC-B DM-DCC-B
DM-TS-A DM-TS-B
or
DM-UTC-B
DM-TS-B
or
DM-UTC-B
DM-UTC-A
DM-RD-A DM-RD-B DM-RD-B
DM-BR-A DM-BR-B
NM-CE-A NM-CE-A
4.2.1.2.7.1 Data
Types
Services utilize communication units, so-called "Application Layer Protocol
Data Units" (APDUs) that are defined in an abstract ASN.8824 syntax in ac-
cordance with ISO Standard 1 to ensure uniform data transfer. Both simple
data types like BOOLEAN, INTEGER and REAL as well as special BACnet
data types are used. These can in turn be nested as SEQUENCE, SET,
CHOICE, etc.
Additional Information
You can find the device-specific data representation of the BACnet Objects
and Services in the documentation of the BACnet Library "BACnet_xx.lib" at
the website
!
Downloads
!
Building
Automation
!
BACnet Downloads
!
Software